K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
E

Fire Extinguisher Mounted Above Allowed Height

The Villa At Traverse PointTraverse City, Michigan Survey Completed on 05-07-2025

Summary

During an observation on May 7, 2025, it was found that the ABC fire extinguisher in the laundry room was mounted at approximately 66 inches above the floor, which exceeds the maximum height allowed by NFPA 10, 6.1.3.8.1. This installation did not comply with the requirements for selecting, installing, inspecting, and maintaining portable fire extinguishers as outlined in NFPA 10. The deficiency was confirmed through an interview with the Maintenance Director at the time of observation. Approximately six occupants could be affected by this deficiency in the event of a fire emergency, as noted in the report.

Plan Of Correction

LSC Annual Survey 5.7.25 K 355 Portable Fire Extinguishers Element 1 The laundry room fire extinguisher was moved down 6 inches to the proper height and validated to be mounted correctly. Element 2 An inspection was performed of all fire extinguishers in the facility to ensure none were mounted any higher than 60 inches. Element 3 The maintenance director was educated on the regulations of tag K 355 in accordance with the NFPA 101 guidance. The regulatory maintenance schedule within TELS was reviewed and deemed appropriate, in addition to all other routine scheduled fire extinguisher inspections. Element 4 The maintenance director will continue to validate monthly per TELS the mounting of all fire extinguishers at the proper height. The NHA will validate these findings with the Maintenance Director. The results of all ongoing audits will be reviewed by the QAPI committee. The NHA is responsible for ongoing compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0355 citations
Blocked Portable Fire Extinguisher Identified
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher next to a resident room was found to be blocked during an observation, and this was confirmed by facility leadership during the exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Monthly Fire Extinguisher Inspections
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation confirming that basement portable fire extinguishers were inspected monthly as required, with no records available for several months. This was confirmed by the Administrator during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation for annual fire extinguisher maintenance and technician certification, and a fire extinguisher in the main kitchen was found blocked. These deficiencies were confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers per NFPA 10
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not ensure portable fire extinguishers were properly inspected and maintained according to NFPA 10, with one extinguisher lacking inspection records and another found overpressurized. These issues were confirmed by the Maintenance Director and could impact 15 occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Accessibility of Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

Surveyors found that 12 out of 18 portable fire extinguishers were installed with the top of the handle positioned above the sixty-inch maximum height allowed by NFPA 101 and NFPA 10, with some as high as sixty-three inches. In one case, a trash can obstructed access to a fire extinguisher cabinet. The Maintenance Director acknowledged these findings during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Fire Extinguisher Maintenance Documentation
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher in the kitchen service hallway was found without the required monthly maintenance and inspection tag, indicating a failure to document compliance with NFPA 10 standards. This was confirmed by the Maintenance Director and Administrator during surveyor interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙