Fire Extinguisher Mounted Above Allowed Height
Penalty
Summary
During an observation on May 7, 2025, it was found that the ABC fire extinguisher in the laundry room was mounted at approximately 66 inches above the floor, which exceeds the maximum height allowed by NFPA 10, 6.1.3.8.1. This installation did not comply with the requirements for selecting, installing, inspecting, and maintaining portable fire extinguishers as outlined in NFPA 10. The deficiency was confirmed through an interview with the Maintenance Director at the time of observation. Approximately six occupants could be affected by this deficiency in the event of a fire emergency, as noted in the report.
Plan Of Correction
LSC Annual Survey 5.7.25 K 355 Portable Fire Extinguishers Element 1 The laundry room fire extinguisher was moved down 6 inches to the proper height and validated to be mounted correctly. Element 2 An inspection was performed of all fire extinguishers in the facility to ensure none were mounted any higher than 60 inches. Element 3 The maintenance director was educated on the regulations of tag K 355 in accordance with the NFPA 101 guidance. The regulatory maintenance schedule within TELS was reviewed and deemed appropriate, in addition to all other routine scheduled fire extinguisher inspections. Element 4 The maintenance director will continue to validate monthly per TELS the mounting of all fire extinguishers at the proper height. The NHA will validate these findings with the Maintenance Director. The results of all ongoing audits will be reviewed by the QAPI committee. The NHA is responsible for ongoing compliance.