K0324 K324: Provide properly protected cooking facilities.
E

Obstruction of Kitchen Hood Fire Suppression System

Plainwell Pines Nursing And Rehabilitation CommuniPlainwell, Michigan Survey Completed on 05-06-2025

Summary

The facility failed to protect cooking facilities in accordance with Life Safety Code (LSC) 19.3.2.5 and NFPA 17A. During an observation, it was found that the shelf of a newly acquired kitchen stove would obstruct the spray nozzles of the hood fire suppression system if activated. This configuration violates NFPA 17A 10.2.7.3, as the obstruction could prevent the suppression system from functioning as intended. The deficiency was confirmed during an interview with the Maintenance Director at the time of observation. No information about specific patients, their medical history, or their condition at the time of the deficiency is provided in the report.

Plan Of Correction

K324 Cooking Facilities Element 1 No residents were harmed due to this deficient practice. All residents and staff have the potential to be affected by this deficient practice. The shelf of the newly installed kitchen stove was removed so that it does not obstruct the spray nozzles of the hood fire suppression system if activated. Element 2 An audit was completed by the maintenance director to ensure that there are no other objects within the kitchen that could obstruct the spray nozzles of the fire suppression system. No other concerns were identified. Element 3 Education was provided to the maintenance director regarding the requirement that there should be no objects obstructing the spray nozzles of the fire suppression system. Element 4 The Maintenance Director or Designee will audit the kitchen one-time weekly for 4 weeks, then monthly times three months, to ensure that there are no objects obstructing the spray nozzles of the fire suppression system. Any concerns will be addressed at the time they are discovered. Audit findings will be presented to and reviewed by the QAPI Committee monthly until such time that consistent substantial compliance has been achieved and maintained as determined by the committee. The Maintenance Director will be responsible for sustained compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Kitchen Hood Inspections and Gas Appliance Restraints
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility failed to maintain the kitchen fire suppression system in accordance with NFPA standards, with only one documented kitchen hood inspection in the prior year and no additional inspection records available despite multiple requests. During the kitchen tour, surveyors also observed that gas-fired appliances lacked restraints to prevent overextension of gas lines when moved for cleaning or service, a finding confirmed by the Maintenance Director. This deficiency had the potential to affect 22 of the 69 residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Michigan

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Michigan — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙