K0324 K324: Provide properly protected cooking facilities.
E

Failure to Complete Required Hydrostatic Testing of Kitchen Hood Fire Suppression System

Iron County Medical Care FacilityCrystal Falls, Michigan Survey Completed on 04-23-2025

Summary

The facility failed to ensure that cooking facilities were protected in accordance with NFPA 96 standards. During a record review, it was found that the kitchen hood fire suppression system in the Cedar Wing had not undergone the required hydrostatic testing, as the two most recent inspection records did not show evidence of this testing being completed. No documentation was provided by the end of the survey to confirm that the hydrostatic test had been performed. This deficiency was confirmed by the Acting Maintenance Director at the time of the record review. This lapse could affect up to 30 occupants in the event of a fire emergency, as noted in the findings.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missed Semi-Annual Kitchen Hood Cleaning
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not complete one of the two required semi-annual kitchen exhaust hood cleanings, as documentation showed only one cleaning was performed and staff confirmed the lack of records for the second cleaning. This affected one smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙