K0371 K371: Have properly sized and located compartments to protect residents from smoke.
B

Smoke Compartment Size Exceeds NFPA 101 Standards

Valley View Haven, IncBelleville, Pennsylvania Survey Completed on 04-23-2025

Summary

The facility failed to comply with the NFPA 101 requirements for smoke compartments on the 1st floor, as observed during a survey conducted on April 22, 2023. The smoke compartment exceeded the maximum allowable size of 22,500 square feet, which is a violation of the standards set for smoke barriers in buildings with a patient bed capacity of 30 or more. This deficiency was confirmed during an exit interview with the Chief Executive Officer and Director of Campus Services on April 23, 2025.

Plan Of Correction

The facility will request the Division of Safety to conduct an FSES Survey.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0371 citations
Lack of Required Smoke Barrier on Resident Sleeping Floor
B
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

A required smoke barrier was not present on a resident sleeping floor with 30 or more beds, as observed and confirmed by the Administrator. This resulted in the floor lacking the necessary subdivision into at least two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Complete Smoke Compartmentalization
F
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility did not provide a smoke barrier map showing complete compartmentalization by smoke barriers throughout the building, as required by code. The map lacked details of smoke barriers separating compartments from outside wall to outside wall, and this was confirmed by Facility Maintenance during record review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Compartment Size Exceeds NFPA 101 Standards
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have smoke compartments exceeding the maximum allowable size of 22,500 square feet in the 400 wing and First Floor, affecting two of four smoke compartments. This was confirmed through observation, document review, and interviews with facility staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Compartment Size Exceeds Maximum Allowance
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have a smoke compartment in the C Wing that exceeded the maximum allowable area of 22,500 square feet, as per NFPA 101 standards. This deficiency was confirmed during an observation and document review, affecting one of four smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Smoke Barriers in Facility
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility did not meet NFPA 101 standards for smoke barriers, failing to install and maintain them to form at least two smoke compartments on every sleeping floor with a capacity of 30 or more patient beds. Observations revealed incomplete smoke barriers throughout the building, confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Facility Exceeds Maximum Smoke Compartment Size
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have three smoke compartments exceeding the maximum allowable size of 22,500 square feet. Smoke compartments one, two, and five were identified as non-compliant during a document review and interview. This issue was confirmed in an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙