K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
D

Failure to Maintain and Test Fire Doors Annually

Chatsworth At Pga NationalPalm Beach Gardens, Florida Survey Completed on 04-15-2025

Summary

The facility failed to maintain and test their fire doors in accordance with NFPA 101, as evidenced by the lack of documentation for the annual inspection of fire door assemblies. During a record review conducted on April 15, 2025, with the Director of Continuum and the Maintenance Supervisor, it was found that the last recorded inspection was dated December 18, 2023. This indicates that the required annual inspection had not been performed within the stipulated timeframe. The Director of Continuum and the Maintenance Supervisor acknowledged the findings during an interview conducted concurrently with the record review. The absence of documentation for the fire door annual inspection was confirmed and discussed with them at the exit meeting on the same day. The report highlights the facility's non-compliance with the NFPA 101 and NFPA 80 standards, which require that fire door assemblies be inspected and tested annually to ensure they are in proper working condition.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0761 citations
Failure to Maintain Self-Closing Fire Door Mechanism
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

A corridor door with a self-closing mechanism leading to the clean utility room by the nurse's station failed to close or self-latch when tested, as confirmed by the Facility Manager. This failure to maintain the fire door in accordance with NFPA 101 and NFPA 80 standards resulted in a deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

Surveyors found that the facility did not provide documentation confirming that fire doors had been inspected within the required 12-month period. The Director of Maintenance confirmed that records of these inspections were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Annual Fire Door Inspections
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not perform a full annual inspection and testing of all rated swinging fire doors, as only the cross corridor fire doors were included while other rated doors, such as those for storage and utility rooms, were omitted. This was confirmed by the maintenance director during record review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Inspect Fire-Rated Attic Access Doors
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to inspect and maintain its fire-rated attic access doors according to NFPA 101 standards. During a fire safety tour, it was found that these doors were not included in the annual inspection, and the Plant Operations Technician was unsure of their inspection status. The Director of Plant Operations confirmed the oversight, acknowledging the findings during an exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to provide documentation of the annual fire-rated door inspection for six smoke compartments. This deficiency was identified during a document review, and the absence of documentation was confirmed during an interview with the Assistant Director of Nursing and the Maintenance Director. The lack of documentation indicates non-compliance with NFPA 80 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Door Labeling Deficiency
E
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not maintain fire doors according to NFPA standards, as fire-rated labels were covered with paint or illegible in the basement and on one resident floor. The Director of Maintenance acknowledged the issue during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

65.1% of Ohio facilities received at least one citation during their inspection in the last 12 months.Will yours be survey-ready?

Surveyors issued 55 serious citations across Ohio in the last 12 months. See exactly what they're citing.

Get ready for your next survey

See what surveyors are citing in Ohio and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙