K0912 K912: Have power receptacles that are properly grounded.
D

Electrical System Deficiency in Laundry Room

Sarah Reed Senior LivingErie, Pennsylvania Survey Completed on 12-17-2024

Summary

The facility failed to maintain electrical system protection in wet locations, specifically on the ground floor laundry room. During an observation, it was noted that electrical outlets were located within six feet of the washing machines and were not equipped with ground fault circuit interrupter (GFCI) receptacles. This deficiency was confirmed through an interview with the maintenance supervisor, who acknowledged the receptacle deficiencies.

Plan Of Correction

1. All three identified outlets in the ground floor laundry room will be replaced with the proper GFCI outlets. 2. All other outlets in the ground floor laundry room will be audited to ensure no other outlets need to be changed to GFCI's, if within 6 feet of a sink. 3. Outlets will be monitored and reported at the next quarterly QAPI meeting/Safety meeting by Director of Maintenance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0912 citations
Failure to Maintain GFCI Protection for Electrical Receptacles
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors identified that three electrical receptacles in the facility were not GFCI protected as required, including those near a sink in the café, a water fountain near the nurse station, and a juice machine in the kitchen. These deficiencies were confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of GFCI Protection on Kitchen Electrical Receptacle
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

A kitchen electrical receptacle near the hand sink was found without required GFCI protection during an observation, and this deficiency was confirmed by the administrator and maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical Outlet Safety and Maintenance
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors found that an electrical outlet near a waterline was not GFI-protected, a damaged outlet faceplate was present in a resident room, and GFI outlets were not tested according to manufacturer instructions. Staff were unaware of these issues, and the deficiencies affected multiple residents and smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-Compliance with GFI Protection Near Water Sources
E
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility was found non-compliant with GFI protection requirements for power receptacles within six feet of a water source in three smoke zones. Observations revealed non-GFI protected outlets in the D Hall Nurses' Station Nourishment Area, B Hall Beauty Shop, and Main Kitchen Prep Area. This was confirmed by the Assistant DON and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Receptacle Deficiency in Laundry Room
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility failed to maintain electrical receptacles in compliance with safety standards in one of over thirty rooms. An observation revealed that the A wing resident laundry room had a washing machine without GFCI protection. This deficiency was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain GFI Protection Near Water Sources
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not ensure that power receptacles were GFI protected within six feet of a water source in one of the smoke zones. Observations revealed non-GFI protected outlets behind an ice machine near a resident room and in the Boiler/Generator Room. This was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙