K0161
E

Building Construction Deficiency in Sprinkler Room

Mountain City Nursing & Rehabilitation CenterHazleton, Pennsylvania Survey Completed on 02-11-2025

Summary

The facility failed to maintain building construction requirements, as evidenced by an observation made on February 11, 2025. During the inspection, a penetration was found in the suspended ceiling portion of the rated ceiling assembly within the Sprinkler Room. This deficiency affects one of the four floors in the facility. The issue was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

Plan Of Correction

Penetration in sprinkler room was corrected. Facility wide audit was completed for like penetrations and addressed. Maintenance will be educated re: K-0161 by NHA/Designee. Maintenance director or designee will audit all areas for 3 months and then quarterly. All findings will be reported at Monthly QPI meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0161 citations
Non-Compliance with Fire Resistance Rating Due to Excessive Building Height
C
K0161
Short Summary

Surveyors found that the facility, classified as a five-story Type II (000) unprotected non-combustible building with a basement, exceeded the maximum allowable number of stories for its construction type, despite being fully sprinklered. This non-compliance with NFPA 101 fire resistance requirements was confirmed by facility leadership and affects the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Follow Up on Building Structural Assessment
F
K0161
Short Summary

The facility did not follow up on a vendor-provided building structural assessment quote that was part of an ongoing plan of correction, as confirmed by document review and interview with the maintenance supervisor. This failure potentially affected the building's structural integrity.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistive Rating Due to Missing Ceiling Tiles
E
K0161
Short Summary

Surveyors found that the facility did not maintain the required fire resistive rating on one floor, as missing rated ceiling tiles were observed in the second floor IT/Conference Room and confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Building Construction Type and Height Requirements
C
K0161
Short Summary

Surveyors found that the facility is a four-story, Type II (000) unprotected noncombustible structure that is fully sprinklered, which exceeds the maximum number of stories allowed by the 2012 Life Safety Code for this construction type. Facility leadership confirmed the building's structure does not meet code requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Building Construction Type and Height Requirements
C
K0161
Short Summary

A survey found that the facility is a three-story, Type II (000) unprotected noncombustible building with a basement, which exceeds the maximum allowable story height for this construction type. The Director of Maintenance confirmed that the building's construction type and height are not permitted under current regulations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Ceiling Penetration in Electrical Room
D
K0161
Short Summary

During a facility inspection, an unsealed four-inch penetration was found in the ceiling of the electrical room, with a conduit passing through. The Maintenance Consultant stated that this resulted from recent utility upgrades where the vendor did not seal the opening after completing their work. The deficiency affected one of two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙