K0363 K363: Install corridor and hallway doors that block smoke.
E

Corridor Door Latching and Obstruction Deficiencies

Premier At Perry Village For Nursing And Rehab, LlNew Bloomfield, Pennsylvania Survey Completed on 12-16-2024

Summary

The facility failed to maintain corridor doors to positively latch and remain unobstructed from closing in two of four smoke compartments. During an observation on December 16, 2024, at 1:20 PM, it was noted that the Main Dining Room double doors, located directly in from the Main Entrance, did not positively latch when closed. This deficiency was confirmed through an interview with the Director of Maintenance at the same time. Additionally, at 1:40 PM on the same day, the corridor door to Resident Room 403 was found to be impeded from closing due to a decoration hanging on the door knob. This obstruction was also confirmed by the Director of Maintenance during an interview conducted at the time of the observation.

Plan Of Correction

1. The main dining room double door was repaired. The decoration was removed from the doorknob of room 403. 2. The Maintenance Supervisor will receive re-education by the administrator on indoor door closure and impeding door closures. 3. The facility will complete an initial audit of all facility doors then 5 random facility doors monthly for 1 year to ensure adequate door closure and no impeded door closures. 4. Audits will be reviewed at the next QAPI meeting. 5. The facility will be in substantial compliance by 2/14/2025.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0363 citations
Failure of Corridor Door to Latch Properly
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that a corridor door to a resident room on one floor failed to latch into the frame when tested, meaning it did not meet NFPA 101 requirements for positive latching of corridor doors. The Facilities Manager and Facility Life Safety staff confirmed during interview that this corridor door did not latch properly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Multiple Corridor Door Deficiencies Impacting Smoke and Fire Protection
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors identified several corridor door deficiencies, including doors that failed to latch, lacked smoke tight integrity, and had missing locksets, across multiple floors. These issues were confirmed by facility leadership during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Properly Latching Corridor Doors
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two corridor doors, one on the third floor and one on the second floor, did not latch when tested, affecting two smoke compartments. The Facility Administrator and Maintenance Director confirmed these deficiencies, which were not in compliance with fire and smoke protection requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Positive Latching of Corridor Door
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

A corridor door leading to the Patio Lounge failed to positively latch within the door frame, as observed and confirmed by the Director of Maintenance. This deficiency affected one of twelve smoke compartments and did not meet NFPA 101 and CMS requirements for corridor door latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Corridor Doors for Smoke Resistance and Latching
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that corridor doors to two resident rooms did not close and latch properly, as confirmed by the facility's Administrator and Maintenance Director. This deficiency affected one of five smoke compartments and did not meet regulatory requirements for smoke resistance and positive latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Corridor Doors Blocked Open with Wedges
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two resident rooms had wooden door wedges holding corridor doors open, preventing them from closing as required for fire safety. Facility staff confirmed that the wedges impeded proper door closure.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙