K0511 K511: Have properly installed electrical wiring and gas equipment.
F

Exposed Electrical Wiring Found in Facility

Manatawny Center For Rehabilitation And NursingPottstown, Pennsylvania Survey Completed on 01-15-2025

Summary

The facility failed to comply with the National Fire Protection Association (NFPA) standards for electrical wiring, specifically NFPA 70, the National Electric Code. During an observation, it was found that there was exposed electrical wiring within an electrical junction box that lacked a cover plate. This issue was located above the suspended ceiling near the cross corridor double doors to Component 01. The observation was confirmed through an interview with the Facilities Director, who acknowledged the presence of the exposed wiring.

Plan Of Correction

1. The Maintenance Director installed a cover plate for the electrical junction box to ensure the wiring is properly protected and secure. 2. The Maintenance Director and relevant staff members will receive training on NFPA 70, National Electric Code, with a focus on proper installation and maintenance of electrical wiring and equipment. 3. The Maintenance Director/designee will conduct a thorough inspection of electrical junction boxes and wiring throughout the facility to verify compliance with NFPA 70 standards. Any additional areas of concern will be addressed immediately. Monthly audits of electrical junction boxes and wiring will be conducted by the Maintenance Director/designee to ensure continued compliance with NFPA 70. Findings will be documented and reported for further action, if necessary. 4. Findings will be reviewed at the Quality Assurance Performance Improvement meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0511 citations
Improper Fastening of Circuit Breaker Panel Cover with Sheet Metal Screws
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that a circuit breaker panel cover in one smoke compartment was improperly fastened with sheet metal screws instead of appropriate blunt-end fasteners, in violation of NFPA 70 requirements. The maintenance director acknowledged the use of sheet metal screws on the panel cover, and the report notes that this noncompliance could result in electric or fire hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Labeled and Maintained Electrical Panels
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors identified that the facility’s electrical system was not maintained according to NFPA 101 and NFPA 70. In the kitchen electrical panel, breakers labeled for the dishwasher were in the off position while the dishwasher continued to run with power. In generator sub panel B, a breaker was labeled for a sprinkler pump even though no sprinkler pump existed, and there was an open breaker position without a blank cover. These issues were confirmed by the Maintenance Director and had the potential to affect all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-GFCI Electrical Outlet Near Sink in Medication Room
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed that an electrical outlet in Nursing Station 1's med room was installed 18 inches from a sink and was not equipped with a required ground-fault circuit interrupter (GFCI), as mandated by NFPA 70, National Electrical Code. The DES confirmed during the survey that this outlet lacked GFCI protection, resulting in a cited deficiency related to utilities and electrical safety in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Electrical Wiring Due to Missing Junction Box Cover
E
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical junction box above the Zone 8 suspended ceiling, near the smoke barrier doors by the Unit Scheduler's Office, was found without a cover plate, leaving electrical wiring exposed. The Director of Maintenance confirmed the issue during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Gas and Electrical Safety Standards
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed multiple deficiencies including broken light bulb bases left in ceiling sockets, combustible materials stored too close to electrical panels, and exposed wiring behind a boiler. These issues were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Broken Electrical Outlet Faceplate at Nurse Station
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical outlet at Nurse Station #2 was found with a broken faceplate, exposing metal terminals. The CMO confirmed the damage had not been previously noticed. Facility policy assigns the Maintenance Director responsibility for maintaining safe equipment, but the exposed outlet was not addressed as required by NFPA 70.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙