F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
L

Failure to Maintain Safe Water Temperatures

Groton Community Health Care Ctr Res Care FacGroton, New York Survey Completed on 12-04-2024

Summary

The facility failed to maintain a safe environment for residents by not ensuring that water temperatures in resident sinks and common shower rooms on the First and Second Floors did not exceed the standard of 110 degrees Fahrenheit. Observations and measurements taken during the recertification and extended surveys revealed that water temperatures were significantly higher, with readings as high as 140 degrees Fahrenheit recorded in facility logs. These elevated temperatures were documented over several months, indicating a persistent issue that was not addressed by the facility's maintenance team. Interviews with facility staff, including the Director of Maintenance and the Administrator, revealed a lack of awareness and understanding of the appropriate water temperature standards. The Director of Maintenance was under the impression that water temperatures should be between 122 and 124 degrees Fahrenheit, which is incorrect according to federal and state regulations. Additionally, the maintenance team did not have a protocol for adjusting water temperatures or documenting corrective actions when temperatures were found to be out of range. The facility's policy on water temperature safety was not effectively implemented, as staff relied on subjective methods, such as testing water with their hands, to determine safety. This lack of proper monitoring and adjustment of water temperatures posed a risk of burns and scalds to residents, although no actual harm was reported. The deficiency was identified as Immediate Jeopardy due to the likelihood of serious harm, injury, or death to residents from exposure to excessively hot water.

Removal Plan

  • The facility had the vendor on site and the water temperature was reduced.
  • The facility completed full house monitoring of temperatures twice per day, logs documented all temperatures were less than 110 degrees Fahrenheit.
  • The facility reviewed their policy for hot water and adjusted it to meet the requirement of 110 degrees Fahrenheit.
  • The facility provided in-service education to 89.8% of staff, with plans for ongoing education of staff not currently on the schedule, prior to the start of their next shift.
  • The survey team interviewed 12 staff from various disciplines, including the two maintenance staff. All staff demonstrated knowledge of education provided regarding water temperatures.

Penalty

Inspection fine: $132,948
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0689 citations
Failure to Ensure Effective Fall Alarms and Supervision
E
F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Short Summary

Failure to ensure effective fall alarms and supervision: two residents had Smart Caregiver monitoring devices set to LOW volume, and one resident's bed alarm did not alert staff before the resident was found on the floor after an unwitnessed fall. One resident had dementia, osteoporosis, prior TIA, and cognitive impairment and was fully dependent on staff, while staff also found that a second resident's bed and recliner alarms did not activate properly during testing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Assess Safety of Perimeter Mattresses
D
F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Short Summary

Failure to assess the safety of perimeter mattresses for two residents. Both residents had severely impaired cognition and significant mobility limitations, and both care plans included use of a perimeter mattress to define the edges of the bed. However, their Mobility, Physical Device, and Fall Risk assessments lacked documentation of a perimeter/defined edge mattress assessment. Staff interviews showed inconsistent understanding of the required order, IDT review, engineering review, and safety assessment before use.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Mechanical Lift Transfers
D
F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Short Summary

Improper Mechanical Lift Transfers: A resident with dementia, spinal cord dysfunction, and dependence for transfers was supposed to be moved with a full-body mechanical lift and two staff members, but a TMA stated she transferred the resident alone. The resident reported that staff sometimes used only one person for lift transfers because of staffing shortages, while other staff and the DON stated this was unsafe and against policy.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe Wheelchair Fit and Incomplete Post-Fall Monitoring
D
F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Short Summary

Two residents were involved in accident-hazard deficiencies. One resident with cancer, PVD, and Alzheimer’s disease was observed in a wheelchair with feet extending past short footrests, with the lower legs resting against the hard footrests despite a care plan entry for padding. Another resident with dementia and a hx of falls had an unwitnessed fall, but ordered orthostatic BP monitoring was not completed accurately and staff reported no post-fall PT referral was received.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to assess electric wheelchair use and update fall interventions
G
F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Short Summary

A resident was given a new electric wheelchair without a prior therapy assessment and could not stop the chair, causing it to strike a bed frame and resulting in a leg laceration, tibia/fibula fractures, and a syncopal episode from blood loss. Another resident with cognitive impairment and high fall risk continued to self-transfer and fall, but the care plan was not updated with new fall interventions after repeated incidents.

Inspection fine: $17,665
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe One-Person Use of Mechanical Lift
E
F0689 F689: Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
Short Summary

A CNA used a Hoyer lift alone to weigh one resident, and another CNA was observed using a Hoyer lift alone to weigh a second resident. One resident’s care plan called for a 2-assist Hoyer lift, and the facility’s lift competency checklist and policy both required two caregivers for mechanical lift use; the DON and Director of Therapy also stated that two staff members are always required.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙