F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
F

Environmental Deficiencies in Facility

The Pavilion Rehabilitation And Nursing CenterNorth Royalton, Ohio Survey Completed on 11-26-2024

Summary

The facility failed to maintain a safe, functional, sanitary, and comfortable environment for its residents, as evidenced by multiple observations during a tour with the Administrator. The elevator, a primary means of transport for residents, had a dirty and worn carpet. The 100 wing had a buildup of dirt along the baseboards, and several resident rooms had issues such as chipped paint, dirt and debris buildup, and dust accumulation. Specific rooms had additional problems, such as cracked showers, bubbled carpets posing trip hazards, and rusted door jams with peeling paint. These deficiencies were confirmed by the Administrator during the observations. Further issues were noted, including a broken window in the common area covered with plywood, which had not been repaired for a week. The 100 hall had multiple unpainted wall patches. The resident Concern/Complaint log revealed multiple complaints about housekeeping and room cleanliness. The facility's policy on maintaining a homelike environment emphasized cleanliness and order, which was not upheld. These deficiencies were identified during the investigation of several complaint numbers.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0921 citations
Loud Violent TV Programming in Secured Unit Dining Area
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

A large-screen TV in the secured unit dining room was playing a loud, violent movie during meals, with screaming, gunfire, crying, and dark scenes visible to residents seated nearby. Two residents with dementia-related cognitive impairment and behavioral issues were directly affected; one became angry and complained the TV was too loud and too dark, while another repeatedly turned off the lights and struck out at an NA when blocked. An LPN, RN, AD, and DON stated the programming was not appropriate for residents with dementia and could increase anxiety or agitation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dirty G-tube Pump and Room Floor
D
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Dirty G-tube Pump and Room Floor: A resident with Parkinson’s disease, DM, and impaired cognition was observed sleeping in bed while connected to a turned-off G-tube pump that had visible dried milk residue, and the room floor also had visible dried milk residue. A CNA confirmed the pump and floor were dirty, and an LVN stated food or milk drippings should be cleaned right away. RN review showed the care plan called for a safe environment with a floor free from spills and clutter, and the facility did not follow its cleaning and disinfection policy.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Poorly Maintained Environment
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and Poorly Maintained Environment: A hole in the ceiling on Hall 100, a detached baseboard in a shower room on Hall 300, dim lighting in the secure unit dining room, and a leaking kitchen ceiling were observed in the LTC facility. Staff and management interviews showed the issues were known or reported inconsistently, and maintenance logs did not document several of the problems. The kitchen leak was being collected in a pot near the food prep area, and the DM stated the kitchen leaked when it rained.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Nonfunctional Bathroom Fixtures
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and nonfunctional bathroom fixtures were observed on two nursing units and in one resident room. A resident reported a broken faucet, and staff observed a replacement knob that wiggled and did not work properly. In one shower room, the hot and cold indicators were reversed, and in another shower room, the drain cover was missing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Unclean Unit Environment
D
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and Unclean Unit Environment: The 200 unit had marred walls, chipped door trim, a large hole in a resident room wall, missing drywall near the offices, and dirt buildup on baseboards, floors, and around the elevator. The dining room and elevator area also had debris buildup, and the elevator door frame wrap was hanging off on both sides. An HSKP staff member stated the facility was down a housekeeper and floors should be cleaned daily.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe Resident Room Conditions Due to Nonfunctional A/C and Biological Growth
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe resident room conditions were identified when multiple rooms had nonfunctional A/C units, temperatures above 81 degrees, and unsealed openings around replacement units. A resident with paraplegia, polyneuropathy, chronic pain, and TBI reported living in a room without working A/C for weeks, while staff said several rooms had been hot for months and administration knew about the issue. Surveyors also observed biological growth inside one A/C unit and on a ceiling tile above a sink in a room occupied by a resident with respiratory concerns.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Ohio

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Ohio — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.