Dishwasher Temperature and Refrigerator Monitoring Deficiencies
Summary
The facility failed to adhere to the manufacturer's instructions regarding the dishwasher temperature, which is crucial for maintaining a safe and sanitary food service environment. Observations and facility records revealed that the dishwasher was operating at temperatures significantly below the required levels since April 2024. Specifically, the wash and rinse cycles were both running at 110 degrees, whereas the operating manual specified a minimum of 120 degrees, with a recommended temperature of 140 degrees. An observation on June 3, 2024, confirmed that the dishwasher was only reaching 100 degrees. The Maintenance Director acknowledged awareness of the issue since April 2024 but indicated that the facility did not own the dishwasher, and the leasing company would need to address the malfunction. Additionally, the facility failed to monitor the temperature of a personal refrigerator in a resident's room, as there was no evidence of temperature checks being conducted per protocol. A CNA confirmed the absence of a temperature sheet for the refrigerator and expressed uncertainty about the procedure for ensuring daily temperature checks. A new order was placed in the electronic medical record on June 3, 2024, directing daily temperature checks to begin the following day. This oversight in monitoring refrigerator temperatures could potentially impact the safety and quality of food storage for the resident.
Removal Plan
- Dishwasher was taken out of use. Regional Maintenance Director contacted EcoLab for dishwasher service.
- Whole house audit completed by Director of Nursing/designee to ensure all plates, utensils and water pitchers were taken out of resident's rooms and not in use.
- All staff will be educated to use paper products for any food or fluid services until the dishwasher is repaired and working at recommended temperatures. Meal service and fluid pass will be observed three times a day to ensure disposable paper products are being used for residents until dishwasher is serviced by Ecolab. Once dishwasher is serviced, staff will be re-educated on manual instructions and machine operations, who to report to when systems are out of range and maintenance to escalate when needing service. Pots/pans and cooking utensils will continue to be cleaned and sanitized via three sink/compartment method.
- Nursing Home Administrator (NHA)/designee will bring results of audits to Quality Improvement Committee (QIC) for review monthly for any additional follow-up and/or in servicing until the issue is resolved and randomly thereafter as determined by QIC.
Penalty
Resources
Below are regulatory guidelines relevant to this citation:
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.
In your survey window? See what surveyors are citing.
The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.