Failure to Maintain Safe Water Temperatures
Summary
The facility failed to ensure that water temperatures in resident bathroom hand sinks and showers were maintained at a safe temperature for two of two nursing units observed. This failure placed residents at risk for serious injury from burns. Observations revealed that the water temperatures in the hand sinks and showers exceeded the safe limit, with temperatures recorded as high as 124 degrees Fahrenheit in some areas. The facility's policy stated that water temperatures should not exceed 100 degrees Fahrenheit, or the maximum allowable temperature per state regulation, but this was not adhered to. Maintenance staff were responsible for checking thermostats and temperature controls and recording these checks in a maintenance log. However, there were no documented temperatures during weekends, and several dates in April 2024 had no recorded temperatures. Interviews with staff revealed that they were unaware of the correct water temperature limits and did not have thermometers available to test the water temperature. Staff were using their hands to test the water temperature, which is not a reliable method to ensure safety. The Director of Maintenance confirmed that the water temperatures were too high and should be between 98 degrees Fahrenheit and 110 degrees Fahrenheit. The facility's mechanical contractors were on site to address a leak in the domestic water storage tank, which may have contributed to the temperature issues. Despite this, the facility failed to maintain safe water temperatures, leading to an Immediate Jeopardy situation for the residents' safety. Staff interviews further confirmed the lack of proper training and equipment to monitor and control water temperatures effectively.
Removal Plan
- The facility immediately suspended showers.
- The maintenance supervisor adjusted the mixing valve and began monitoring.
- Any residents who received a shower has been assessed by nursing staff to ensure no injuries have occurred.
- The facility mechanical contractors were on site and completed repairs to the hot water holding tanks.
- The facility water policy on water temperatures and showering/bathing has been updated to include staff ensuring the water temperature is within acceptable range and to not give shower/bath.
- Staff were immediately educated includes teaching staff how to properly test the water prior to giving the shower, and notify maintenance when temps are above the 110 requirement.
- Thermometers have been placed in each shower room.
- Staff in servicing has begun and will continue until all nursing staff have been educated. The staff will be in serviced either in person or over the phone. Our system tracks individual signs offs of the notifications, followed by an in person/phone in-service.
- The facility will continue random temperatures monitors every shift through nursing supervisor, the maintenance supervisor will also complete temperature logs daily in the AM and again at the maintenance shift.
- If the Maintenance director cannot be reached the Administrator will be notified if temperatures are found over 110.
- Both logs will be summarized and reported to QAPI (Quality Assurance Program Improvement), with any trends and effective interventions.
Penalty
Resources
Below are regulatory guidelines relevant to this citation:
Trusted data from CMS and state health departments
Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.
In your survey window? See what surveyors are citing.
The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.