F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
E

Deficient Resident Call System Maintenance

Steuben Center For Rehabilitation And HealthcareBath, New York Survey Completed on 05-17-2024

Summary

The facility did not properly maintain the resident call system in three resident units (Keuka, Lamoka, and [NAME]). Specifically, elements of the nurse call system were not functioning properly, and modifications made to parts of the call system did not relay the call directly to a staff member or centralized workstation. A resident complaint was documented in the 'Resident Council: Meeting Minutes' about a broken call light/pull cord in their bathroom, and they were given a tap bell, which the resident did not feel was adequate. Observations revealed that the 'Call to U' brand wireless caregiver pager system was used as a temporary fix, but it had significant limitations, such as only ringing twice and not indicating which resident pressed the call bell, making it difficult for staff to respond promptly and accurately to calls for assistance. Certified Nursing Assistant #2 confirmed that the 'Call to U' system was implemented due to issues with the 'Jeron' push button call lights in several rooms, where some lights turned on without making a sound, and others had no lights or sounds at all. The Director of Maintenance acknowledged the problems with the nurse call system, stating that an electrician was scheduled to address the issues, and the 'Call to U' system was a temporary solution. However, the temporary system had faults, such as the receiver boxes only staying lit for a few seconds and not being carried by staff, which further complicated the ability to respond to calls. Additional observations and interviews revealed that the central nurse call monitoring screens on the Keuka and [NAME] Units were not functional, and the Director of Maintenance admitted that the call system was obsolete. The facility had a proposal in process to replace the call system on the second floor Lamoka Unit and planned to use the parts removed to fix other issues. Despite these plans, the current state of the call system posed a significant deficiency in ensuring residents' ability to summon assistance effectively.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0919 citations
Call Light Not Within Resident’s Reach
D
F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
Short Summary

Call Light Not Within Resident’s Reach: A resident with Parkinson’s disease, dementia, unsteadiness, and a fall history did not have an accessible call light while seated in his wheelchair watching TV. The call light was taped to a positioning pole near the bed, and both the resident and staff confirmed he could only use it if he moved his wheelchair back to the bed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Call Light Pad Not Available for Resident With Limited Hand Function
D
F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
Short Summary

A resident with functional quadriplegia and stiff, curled fingers did not have an adaptive call light pad in the new room after readmission and was observed using a standard call light button with difficulty. Records showed the resident had previously used a call light pad, but the room was equipped with a standard button instead of the easier-to-use device noted in the resident’s history and care documentation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonfunctioning Call Device Not Available to Resident
D
F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
Short Summary

A resident dependent on staff assistance with ADLs had a nonfunctioning call device after the cord was found wrapped on the siderail. When the resident activated it, neither the wall box nor the overhead indicator light illuminated, and the ADON and Maintenance Director both confirmed the device was not working. The resident had COPD, morbid obesity, HTN, and moderately impaired cognition, and the care plan directed staff to keep the call light within reach for toileting and incontinence assistance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unanswered and Malfunctioning Call Light System
E
F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
Short Summary

Unanswered and Malfunctioning Call Light System: A facility failed to maintain a fully functional call light system when pagers, the nursing station notification terminal, and the reset function did not reliably alert staff. Several cognitively intact residents who needed extensive assistance reported long waits for help, repeated unanswered call light activations, and in some cases bladder and bowel accidents. Staff interviews confirmed that pagers sometimes did not work, the app at the nurses’ station was unreliable, and the system could reset after multiple alerts without staff response.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Nonworking Bedside Call Light
D
F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
Short Summary

Nonworking Bedside Call Light: A resident with Parkinson’s disease, dementia, weakness, and impaired coordination had a bedside call light that did not work when she pressed it while in bed, and the hall indicator did not light up. A CNA confirmed the failure, while the Maintenance Supervisor and DON were unaware the call light was not working. An email from the ADM noted there was no policy for call lights.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Call Light Not Kept Within Resident Reach
D
F0919 F919: Make sure that a working call system is available in each resident's bathroom and bathing area.
Short Summary

Call Light Not Kept Within Reach: A resident with chronic respiratory failure with hypoxia and paroxysmal atrial fibrillation, who was cognitively intact and needed partial/moderate assist with transfers, was found unable to reach the call light. The resident believed it was near the bed, but staff located it behind the head of the bed near the wall and placed it beside the resident. The facility policy required a call light or bell access to be kept within reach.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.