F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
F

Failure to Regularly Inspect Bed Frames for Entrapment Risks

New England Homes For The Deaf, IncDanvers, Massachusetts Survey Completed on 03-21-2024

Summary

The facility failed to regularly inspect bed frames to identify areas of potential entrapment, specifically in Zone 7 (the space between the mattress and the foot of the bed) for all 27 residents' beds. This deficiency was evidenced by the inadequate bed bolster provided for a resident with a traumatic brain injury and severe cognitive impairment. Observations revealed a visible gap between the bolster and the mattress, creating a potential entrapment risk. The resident's bed rail assessment and care plan did not address this entrapment zone, and the facility's documentation of bed inspections was outdated, with the most recent records from 2021. Interviews with the Maintenance Director and Unit Manager confirmed that bed entrapment checks were only conducted annually, and there was no recent documentation of these inspections. The Unit Manager acknowledged the inadequacy of the bolster and the entrapment risk it posed. The Administrator was unable to explain why the entrapment zone sheets had not been updated since 2021. This lack of regular inspection and documentation led to the failure to identify and mitigate the entrapment risk for the resident.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0909 citations
Incompatible Mattress and Bedframe for Dependent Resident
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

A resident with severe cognitive impairment and multiple neurologic and vascular diagnoses was observed on multiple occasions lying on an air mattress that was too small for the bedframe, resulting in the resident’s feet and head extending beyond the mattress and a gap of about one foot between the mattress and the bedframe. A CNA, the ADON, and the DON each confirmed that the mattress did not properly fit the bedframe and did not accommodate the resident’s height.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documented and Ongoing Bed Safety Inspections
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

The facility failed to maintain a documented, routine program for inspecting bed frames, mattresses, and bed rails for safety and entrapment risks. Although a resident’s bed and four other beds with air mattresses and side rails were observed by the DON and found to have proper mattress fit and no unsafe gaps, the Maintenance Supervisor stated that while he measures and assesses beds for proper fit and entrapment hazards when placing new mattresses, he does not document these assessments and does not perform regular, scheduled safety checks of all beds.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Inspect and Document Safety of Beds and Bed Rails per MIFU and FDA Guidance
F
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

Surveyors found that the facility did not conduct or document required safety inspections of any of the 77 resident beds, including those with assist or mobility bars. The NHA confirmed there was no policy for bed inspections, and the Maintenance Director reported that while informal checks are done at admission (such as removing safety bars, checking for a mattress, testing remotes, and looking for exposed wires), these checks are not documented. Review of the MIFU for Joerns beds showed a requirement for monthly visual inspections for broken welds, cracks, and loose hardware, which were not documented. Additionally, although FDA guidance on seven bed entrapment zones and dimensional limits was available, the Maintenance Director stated that FDA entrapment zone measurements were not performed or documented for any of the 36 residents using bed rails, mobility bars, or assist bars.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incompatible Mattress and Bed Frame Resulting in Unsafe Bed Setup
D
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

A resident with multiple medical conditions was found to have a low air loss mattress that overhung the bed frame by about five inches, preventing the installation of a grab bar on one side. The Maintenance Director confirmed the mattress was too large for the frame and not fully supported.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Regular Bed Safety Inspections and Maintenance
F
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

The facility failed to perform regular inspections and maintenance of bed frames, mattresses, and bed rails for multiple residents, as required to identify possible entrapment areas and ensure that bed components were safely attached. During interviews, the DON and the Administrator confirmed that bed evaluations, assessments, and routine maintenance had not been completed as expected and acknowledged that this did not meet their own safety expectations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Conduct and Document Routine Bed and Side Rail Safety Inspections
E
F0909 F909: Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
Short Summary

The facility failed to conduct and document routine safety inspections of bed frames and side rails used by a resident with intact cognition who was repeatedly observed in bed with bilateral quarter side rails in the up position around the shoulders and head. The maintenance supervisor reported that beds and rails were only checked and repaired when issues were reported, and there was no established program for routine inspections. The DON believed beds and rails were inspected before use but confirmed there was no documentation of such inspections and no policy or procedure governing bed frame and bed rail use and inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release May 27, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙