Improper Use of Extension Cords for Electrical Equipment
Penalty
Summary
A deficiency was identified when, during an observation in the Wynona Den Office, a fan was found plugged into an extension cord, which was then plugged into another extension cord to supply power. This setup was confirmed by both the Facilities Director and the Administrator at the time of discovery. The use of extension cords in this manner does not comply with NFPA 70, section 400.8, which prohibits the use of extension cords as a substitute for permanent wiring. The report notes that this practice could affect two occupants in the event of an electrical overload or short circuit.
Plan Of Correction
K920: Electrical Equipment - Power cords and Extension cords The facility will ensure that power strips are in compliance with code and that extension cords are not used. This will be accomplished by: The facility will work with the Facilities department to have an additional electrical outlet installed in the wall. The facility will educate all staff that extension cords are not to be used and that power strips need to meet code requirements. All staff will sign off on this education. The facility will work with the staff member who uses this office to educate them that extension cord use is prohibited, and this staff member will sign an attestation of understanding that they will not use inappropriate power strips or extension cords. This employee's office will be audited weekly for 3 months to ensure compliance.