F0908 F908: Keep all essential equipment working safely.
D

Failure to Timely Repair Malfunctioning A/C Unit

Kensington Gardens Rehab And Nursing CenterClearwater, Florida Survey Completed on 06-12-2025

Summary

The facility failed to ensure timely repair of essential equipment, specifically one of the rooftop air conditioning (A/C) units, identified as unit #11, out of a total of 19 units. According to staff interviews and observations, the A/C unit #11 had a bent fan blade and had not been functioning properly since October 2024. The maintenance assistant was aware of the ongoing issue, but the Nursing Home Administrator (NHA) stated she was unaware of the problem until it was brought to her attention during the survey. During the survey, staff were observed attempting to find cooler areas in the building, indicating discomfort due to the malfunctioning A/C. The facility did not have a policy in place for the maintenance and repair of A/C units. Maintenance staff confirmed that the issue with A/C unit #11 had persisted for several months without resolution. The NHA could not confirm whether payment had been made to the A/C company for previous repair requests, and only a new quote for repairs was available at the time of the survey. The lack of timely repair and absence of a maintenance policy contributed to the deficiency cited by surveyors.

Plan Of Correction

F908: What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: The AC unit (#11) in the south hallway/activities room area repaired by 7/12/2025. How you will identify other residents having potential to be affected by the same practice and what corrective actions will be taken: An audit of the roof top AC units in the facility was completed. Roof top AC units identified with concerns will be repaired and/or replaced by 7/12/2025. What measures will be put into place or what systematic changes you will make to ensure that the practice does not recur: 1. By 7/12/2025, Staff educated by the Administrator and/or designee on essential equipment, safe operating condition and identified concerns to be reported via TELS. 2. Newly hired staff will be educated on essential equipment, safe operating condition and identified concerns to be reported via TELS. How the corrective action (s) will be monitored to ensure the practice will not recur, i.e., what quality assurance program will be put in place: The Administrator and/or designee will conduct a random audit of the roof top AC units to ensure essential equipment is in safe operating condition weekly for 4 weeks, then monthly x 3 months. The findings of the audits will be reported to the QAPI committee monthly until the committee determines substantial compliance is sustained.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Expired Supplies Found in Crash Carts
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Expired supplies were found in two crash carts on nursing units 1B and 2B. An opened Ambu bag in the 2B cart was expired, and the 1B cart contained two expired Ambu bags and expired Assure Prism glucometer strips. RN staff confirmed the items were expired and should not have been in the carts.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Stove Burner Not Functioning
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

A gas stove in the kitchen had a back center burner that would not ignite when turned on, and staff reported it had been not working for about 1 to 2 months. Interviews showed cooks were expected to report equipment problems to the DM, who would notify Maintenance, but the issue was not promptly communicated to Maintenance. No gas odor or hissing was observed, and the burner was later taken out of service until repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Elevator Malfunctioned and Remained in Need of Repair
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep one of its elevators in safe operating condition. Records showed elevator two malfunctioned multiple times and needed a replacement part, and residents and staff were aware of the repeated malfunctions. The Administrator confirmed the elevator was malfunctioning and needed repair.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Dryer Lint Traps
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Failure to Maintain Dryer Lint Traps: Surveyors observed heavy lint buildup in both dryer lint traps, with lint hanging from each trap and covering the full trap surface. The sign-off log showed no entries after the prior shift, and staff interviews confirmed the required two-hour checks and documentation were not consistently completed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Glucometer Calibration and Quality Control Not Documented
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Glucometer calibration and QC were not documented for one glucometer on Medication Cart D, and the QC log was blank for the scheduled check. LVN and DON verified that the 11-7 shift was responsible for nightly/daily calibration and QC to support accurate blood sugar readings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Thermostats Not Powered On or Working
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Thermostats Not Powered On or Working: Two of five sampled thermostats were observed turned off with black screens and no visible power. A resident’s RP said it was always hot in the resident’s room and a fan was provided because there was no working AC. The MS stated the thermostats should be on and working to regulate room temperatures, but he was unsure how often they should be checked.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Florida

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Florida — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.