F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
B

Resident Bedrooms Below Required Square Footage

Bel Vista Healthcare CenterLong Beach, California Survey Completed on 05-18-2025

Summary

The facility failed to ensure that two of its resident bedrooms met the required minimum square footage per resident, as specified by federal regulations. Specifically, two multi-bed rooms were found to be below the 80 square feet per resident requirement, and two single-bed rooms were below the 100 square feet requirement. This was identified through a review of the facility's Client Accommodations Analysis form and confirmed by direct measurement during an observation with the Maintenance Supervisor, who acknowledged the rooms were small for two beds and was unaware of the correct measurement standards. The Director of Nursing also confirmed that rooms deemed too small could become cluttered, potentially leading to falls due to insufficient space.

Plan Of Correction

F-tag 912 I: Corrective Action for residents found to have been affected: • On 06/09/2025, the Social Services Director/designee conducted a room visit to residents in rooms 5 and 6. No signs or indications of any adverse effects from being in a room with more than occupancy required. Resident's feel safe, privacy not invaded, and no negative outcomes with care and treatment. Current needs are met. II: Facility's identification of other residents having the potential to be affected by the same deficient practice and corrective action taken: • On 06/09/2025, the Maintenance Director updated the room measurements for all rooms to ensure residents have adequate space for care, access and use of assistive devices and furniture and for visitors. • All other rooms are in compliance. III: Measures and systemic changes put in place to ensure deficient practices do not recur: Application for the room waiver was sent to Feven Isaac on 06/10/2025. Department managers will conduct room rounds daily to ensure resident satisfaction and validate through feedback. IV: Facility's plan to monitor corrective actions are achieve & sustain compliance; Integrate the POC to QA Process: • The Social Services Director/designee will report findings of the daily room rounds during the monthly QAA meeting x 3 months for compliance. • Trends and patterns will be discussed for further recommendations and interventions. • The administrator will monitor compliance. V. Corrective Action Completion Date: 6/12/2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0912 citations
Insufficient Room Size in Multiple Resident Bedrooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Insufficient Room Size in Multiple Resident Bedrooms: The facility failed to ensure four semi-private rooms met the required minimum of 80 sq. ft. per resident. The ADM stated the rooms were in an unused area awaiting renovation, but they remained listed on the bed classification form. The ADM also stated the facility had no policy for the room size waiver and confirmed the rooms were not planned to open in the near future.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Resident Rooms Did Not Meet Required Square Footage
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Resident Rooms Did Not Meet Required Square Footage: Based on record review and interviews, 14 of 15 resident rooms inspected did not meet the required square footage per resident for privacy and comfort. The Bed Classification Form showed a 144-bed capacity, and the Administrator stated she was not aware of any room waivers. Measurements identified multiple rooms with less than 80 sq ft per bed, and the Administrator later confirmed the form was accurate and said she could not advise that a waiver request had been submitted previously.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Shared Rooms Did Not Provide Required Floor Space
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

Shared rooms did not provide the required 80 SF per resident in 23 rooms. A census report showed multiple rooms with three residents or capacity for three residents, and a tour confirmed the room arrangements. The DON stated bed management meetings did not address moving residents to meet the space requirement, and the administrator said current residents were not informed when a bed opened unless they requested a room change. One room measured 230 SF, providing 76.67 SF per resident when occupied by three residents, and a resident stated more space would be helpful for belongings and movement.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Space in Multiple-Resident Rooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

A facility failed to ensure 14 of 33 resident rooms met the required 80 sq ft per resident for multiple-bed rooms. Although the ADM requested a room waiver and staff, residents, and the ADON, DON, DOR, and ADOR stated there was enough room for care, movement, ADLs, and therapy, the Client Accommodation Analysis showed several three-bed rooms measured only 72.1 to 79.8 sq ft per resident, below the required standard.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Room Size in A-Wing Single Resident Rooms
B
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

The facility failed to ensure that 13 single resident rooms on the A-wing met the required 100 sq ft of usable floor space, and 6 occupied rooms were identified as noncompliant. The DON confirmed the rooms did not meet the standard, while an RN reported no resident complaints about room size and the Administrators stated they had no requests for room moves or complaints from current residents. One resident said staff care was not inhibited by the room size, and the facility reported it had previously moved a resident to a larger room for family visiting needs.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Required Minimum Square Footage in Multi-Occupancy Rooms
D
F0912 F912: Provide rooms that are at least 80 square feet per resident in multiple rooms and 100 square feet for single resident rooms.
Short Summary

The facility failed to meet regulatory and policy requirements for minimum usable living space in multi-occupancy resident rooms. Policy required at least 80 sq ft of usable floor space per resident in semi-private rooms, but surveyor measurements of multiple bed areas in two rooms, conducted with the maintenance director, DON, and later the administrator, showed bed spaces ranging from about 47 to 75.33 sq ft, even when adjacent common areas were included. The administrator confirmed that these room sizes were below the required minimum.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across California

Get a heads-up on the newest immediate-jeopardy (J–L) citations in California — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙