K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Transmit Fire Alarm Signals to Central Station

Santa Paula Post Acute CenterSanta Paula, California Survey Completed on 04-22-2025

Summary

The facility failed to maintain its fire alarm system in accordance with NFPA 70 and NFPA 72 requirements. During a tour, observation, and record review, it was found that the fire alarm system did not transmit fire signals to a central station when initiating devices were activated. Three devices were tested within a specific time frame, and none of the alarm signals were received by the central station. The Maintenance Supervisor confirmed during an interview that after testing the devices, he contacted the central station, which verified that no trouble signal had been received. This failure to transmit alarm signals was directly observed and documented during the survey process. The deficiency affected all 79 residents in the facility, spanning three smoke compartments. The Assistant Administrator confirmed the issue and attributed the problem to a possible phone service provider issue, but at the time of the survey, the fire alarm system was not functioning as required to ensure prompt transmission of fire signals to the central station.

Plan Of Correction

K 345 K345 Fire Alarm System - Testing and Maintenance K345 CORRECTIVE ACTION: ADON/Maintenance upon discovery of the alarm testing signal transmission failure to service provider: Fire watch protocols were activated per facility policy. SEE EXHIBIT - A - Fire alarm service provider (Bay Alarm) dispatch was contacted to follow up on the testing transmission disruption. - Facilities IT and telephone service provided (Frontier) were contacted to troubleshoot the communication lines. - SEE EXHIBIT - B - Bay Alarm technician inspected fire alarm panel on and reported that it was in good functioning order. - Technician referred our maintenance team to follow up with our phone service provider. K345 CORRECTIVE ACTION: ADON/Maintenance upon discovery of the alarm testing signal transmission failure to service provider: Fire watch protocols were activated per facility policy. SEE EXHIBIT - A - Fire alarm service provider (Bay Alarm) dispatch was contacted to follow up on the testing transmission disruption. - Facilities IT and telephone service provided (Frontier) were contacted to troubleshoot the communication lines. - SEE EXHIBIT - B - Telephone service provider technician inspected the telephone lines and reported that one of the land lines likely had physical damage. - Technician re-routed the landline and re-established connection to the fire alarm panel. - While technician was in the building, our maintenance team reached out to Bay Alarm to inform their central monitoring station that a test of the system would be performed. - Bay Alarm emailed the test report confirming that the test signal was received. - SEE EXHIBIT - C IDENTIFICATION OF OTHERS: Maintenance Dept/Designees were inserviced to include the monthly testing results in the monthly quality assurance meeting report. Designee will also include communication with the central station prior to system testing and include confirmation of patent signal in the monthly report. - SEE EXHIBIT - D MEASURES TO PREVENT RECURRENCE: Maintenance Dept/Designees were inserviced to inform administration during daily department manager morning meeting/report whenever testing is taking place to ensure administration is able to monitor the testing and confirm successful testing and transmission to providers' Central Station. - SEE EXHIBIT - E

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Failure to Perform and Document Annual Duct Detector Differential Testing
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Properly Test Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and properly test multiple fire alarm system components, including smoke detectors near the medical supply area and house laundry that could not be located, elevator fire hat and primary recall functions that could not be reset due to lack of a key, and an untested elevator control shunt trip. On revisit, the missing smoke detectors had been replaced with battery-operated units that were not connected to the building’s fire alarm notification system, and the previously identified fire alarm issues remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Fire Alarm System Inspection and Testing Documentation
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain required inspection and testing documentation for its fire alarm system. During surveyor review, no records could be produced to show that semi-annual visual inspections or the two-year smoke detector sensitivity testing had been completed, and the maintenance supervisor confirmed that this documentation was unavailable at the time of the survey. This deficiency affected the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Fire Alarm Documentation and Testing Records
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain required fire alarm system documentation and testing records. During record review with the Maintenance Director, there was no vendor-signed log book at the fire panel documenting work performed at each visit, no documentation of biennial smoke detector sensitivity testing, and no fire alarm system design plans located at the fire panel, as required by NFPA 101 and NFPA 72.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Proper Working Order
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors identified that the facility did not maintain its fire alarm system in accordance with NFPA 72 when the fire alarm control panel was observed displaying a trouble signal. During the observation, the Maintenance Director confirmed that the trouble condition was related to a faulty heat detector. This unresolved trouble indication showed that the fire alarm system was not being properly maintained to ensure it functioned as designed for the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across California

Get a heads-up on the newest immediate-jeopardy (J–L) citations in California — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙