F0880 F880: Provide and implement an infection prevention and control program.
L

Failure to Implement Effective Water Management and Infection Control for Legionella

Circle Of CareSalem, Ohio Survey Completed on 04-09-2025

Summary

The facility failed to develop, implement, and follow a comprehensive and effective infection prevention and control program, specifically regarding its water management plan to prevent the growth and spread of legionella bacteria in the water supply. Despite receiving water test results indicating elevated and increasing levels of legionella, the facility did not re-evaluate or update its water management risk assessment or plan, nor did it provide effective interventions to mitigate the risk. The facility also did not ensure that residents were prevented from accessing or using water from areas where legionella could be present, as evidenced by residents continuing to use sinks and showers in affected areas without appropriate filters or signage restricting use. The facility's water management risk assessment was outdated and lacked critical components such as summaries, acceptable control levels, and response procedures for positive legionella findings. Maintenance activities were inconsistently documented, with no evidence of routine maintenance or cleaning of showers, whirlpools, or flushing of water in unoccupied rooms as required. Water testing was limited to a single location, and when results showed a significant increase in legionella levels, there was no documented investigation or intervention. Staff interviews confirmed a lack of awareness of the severity of the test results, and there was no evidence that residents were assessed for symptoms of Legionnaires' Disease during the period of elevated risk, including those with respiratory symptoms or hospitalizations. Residents, including those with high-risk conditions such as tracheostomies, ventilator dependence, and those receiving dialysis, continued to use water sources that were potentially contaminated. Interviews with residents confirmed ongoing use of sinks and showers in areas where legionella was present, and staff confirmed that there were no effective restrictions or visual cues to prevent such use. The facility's infection surveillance system was also found to be ineffective, as it failed to track infections and monitor trends, and appropriate infection control techniques were not followed during wound care for at least one resident.

Removal Plan

  • An all-staff in-service was completed on risks, signs and symptoms and interventions for legionella by the DON and IP Nurse #302.
  • Water to each sink in all facility rooms was shut off to prevent accidental use by residents and staff. Gallon jugs of purified water were put in place to wash hands with dates and names on each.
  • The DON/designee would audit employee call-offs weekly, monitoring for any symptoms related to legionella illness. Any concerns would be immediately reported to the Administrator and addressed by the Quality Assessment Performance Improvement (QAPI) committee as necessary.
  • The facility contracted with PT enterprises to assist with the water management plan. PT enterprises took twelve water samples (four swabs and eight additional 250 ml potable water samples).
  • Point of use filters for all water sources in the facility were ordered.
  • The DON brought in hot and cold-water dispensers for use on the second and third floors. This water was provided for residents' use for any residents who did not want to drink bottled water and staff were responsible for bringing the water to residents. Additional bottled water was supplied to the fourth floor.
  • The DON educated the weekend staff and agency staff working on-site on not using the room sinks or shower on the second floor, as well as signs and symptoms of legionella.
  • A Legionella assessment data collection form was created in point click care (PCC), which included a set of vital signs, a review of potential symptoms of legionella, a place for a narrative, and a yes or no question as to whether or not the resident experienced more than three symptoms beyond their baseline.
  • All nurses would be educated on this form. Any nurse not educated would not be allowed to work the floor until the education was completed. Nurses would complete this assessment on resident admission and with resident change of respiratory condition.
  • New legionella filters were received and placed on the main floor bathroom sink, therapy room sink, room [ROOM NUMBER] sink faucet, shower heads on the second, third and forth floors, at the nursing station sinks on the second, third and forth floors and on the dialysis center sinks by Maintenance Manager #322.
  • Legionella tests for six residents who were transferred from the facility for signs and symptoms of respiratory distress were completed.
  • A contracted plumbing company ([NAME] Plumbing) came to the facility to evaluate appropriate adapters to fit on the sink filters. They also evaluated sanitation. The water remained off to the room sinks at this time.
  • The DON/designee completed resident assessments (legionella assessment data collection form) for all facility residents. The resident assessments would continue to be conducted weekly by the DON/designee and/or Infection Preventionist. Any concerns would be immediately reported to the Administrator and Medical Director for follow-up.
  • The facility Water Management Committee, including the Administrator, DON, IP #302, Maintenance Manager #322, Housekeeping/Laundry Supervisor, RT Director and Dietary Manager met to further discuss the facility's Water management -Legionella plan.
  • The facility QAPI committee met to review any updates to the water management plan and complete audits.
  • The facility new water management protocols included: a.) Each faucet and shower head aerator would be cleaned with an approved scale and lime build-up cleaner semi-annually to ensure proper water flow quarterly. b.) The hot water boilers would be set at 140 or greater. Facility staff would record the temperature of each hot water device weekly and adjust immediately if less than 140. To ensure compliance to policy, staff would retest the following day to confirm appropriate temperature. c.) Hot water holding tanks would be set at a minimum of 140 to inhibit the growth of Legionella and other opportunistic pathogens. Facility staff would record the temperature weekly and adjust immediately if less than 140 to ensure compliance. d.) Regular cleaning and changing of filters would be done per manufacturers' recommendations. The facility would remove scale and clean using approved cleaning agents semi-annually and changing the filters every six months or per manufacturer recommendations. Maintenance Manager #322 would audit monthly to ensure compliance and audits will be reviewed in QAPI meetings. e.) Weekly flushing of water would be added to housekeepers assignments which would consist of flushing for three minutes each faucet and showers also flush all toilets at least once every week. The supervisor would review documentation weekly to ensure compliance. Audits would be reviewed, and the facility would determine where the failure occurs during QAPI meetings. f.) If the facility experiences one or more positive cases of legionellosis, the facility would conduct semi-annual testing to determine if the water management plan (WMP) was effective in controlling legionella and the Maintenance Manager #322 will follow up with the vendor to determine failure to conduct and correct this. g.) For any positive legionella in the water, the facility would contact PT enterprises, to conduct testing on water samples, provide alternate water sources for bathing and patient care, inspect all faucets for built-up scaling and cleaning with appropriate cleaner and replace all filters on incoming water sources. h.) Legionella filters would be changed per manufacturers' recommendations.
  • The facility received ordered parts which were being installed with a plan to have all installation of parts/filters completed.

Penalty

Inspection fine: $179,23514 days payment denial
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0880 citations
Failure to Use EBP, Perform Hand Hygiene, and Maintain Sanitary Laundry Practices
E
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

A resident with an indwelling Foley catheter had EBP identified in the care plan, but staff did not consistently wear gowns during close contact care, including vital signs, medication administration, hygiene-related contact, and topical treatment. In addition, a TMA administered medications to three residents without sanitizing hands between residents or before handling medications, despite policy and DON expectations requiring hand hygiene. Laundry practices were also inconsistent with sanitary handling, as staff sorted soiled laundry without gowns and gloves being available in the room and reported using only gloves for most dirty laundry tasks.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Infection Control Lapses During Insulin Administration
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

An LVN failed to follow hand hygiene and insulin pen preparation practices during a medication pass for a resident with diabetes. After washing his hands, he turned off the faucet with his bare hand, then administered insulin without cleaning the insulin pen’s rubber seal with alcohol first. The DON stated both actions were a break in infection control, and the facility policy required proper hand hygiene and noted that gloves do not replace hand hygiene.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Hand Hygiene During Wound Care
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

Failure to perform hand hygiene during wound care was identified for a resident with a stage 4 coccyx pressure ulcer, diabetes, CAD, and HTN. An RN and the ADON provided perineal and wound care, but the RN repeatedly changed gloves without sanitizing hands and did not sanitize hands or change gloves before removing soiled packing and applying new wound packing and a dressing. The DON stated staff were expected to sanitize hands every time gloves were removed, and facility policy required hand hygiene after glove removal and before moving from a contaminated body site to a clean body site.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Infection Control Failures During Medication Pass and Respiratory Equipment Storage
D
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

An RN failed to follow hand hygiene and safe medication handling during med pass, including touching dropped tablets and handling meds without gloves or hand hygiene between steps. The facility also failed to store nebulizer mouthpieces and masks in labeled bags when not in use for residents receiving respiratory treatments, including a resident with CHF, CKD, DM2, and anemia. The DON confirmed the expected storage and handling practices were not followed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Cleaning of Community-Use Glucometer
E
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

An LPN was observed cleaning a community-use glucometer with an alcohol pad instead of the bleach wipe or equivalent required by the facility policy. The LPN stated he always used alcohol pads, while the DNS stated staff were to use bleach wipes. The glucometer was used for CBG checks on several residents with diabetes, and their records did not indicate a BBP.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Use PPE During Wound Care and Replace Oxygen Tubing Timely
E
F0880 F880: Provide and implement an infection prevention and control program.
Short Summary

A resident with MRSA and an abdominal wound was observed during wound care with contracted wound care staff entering without proper PPE, touching room items, and performing wound care without consistent hand hygiene or glove changes while moving from dirty to clean tasks; the same staff then went to another resident’s room without gowns despite EBP signage. The facility also failed to timely replace another resident’s oxygen tubing for CPAP/oxygen use, and the tubing had no label showing when it was last changed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Ohio

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Ohio — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.