K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Test Fire Alarm Interface Equipment

Creekside Health And Rehabilitation CenterSarasota, Florida Survey Completed on 04-03-2025

Summary

The facility failed to test fire alarm interface equipment in accordance with NFPA 72, which could result in smoke detection devices failing to operate as designed, thereby endangering the occupants of the building. During a review of the facility's fire alarm inspection report, it was found that the report did not include complete results for the differential pressure testing of the duct smoke detectors. The report listed eight detectors in the system, but only four were reported as having been tested. Additionally, the report did not indicate that the sensitivity had been tested on any of the duct detectors. Further communication with the facility revealed that only five out of the eight detectors were tested, and there was still no indication that sensitivity tests were completed on any of the detectors. Differential pressure testing of tube-type duct detectors is a requirement of NFPA 72, and the failure to conduct these tests as required could compromise the safety of the building's occupants in the event of a fire.

Plan Of Correction

Preparation and/or execution of this plan does not constitute admission agreement by the provider of the truth of the facts alleged or conclusions set forth in the statement of deficiencies. This plan of correction is prepared and/or executed solely because it is required. 1. What corrective actions will be accomplished for those residents found to have been affected by this deficient practice. On 04/10/25 differential pressure testing of the smoke detectors was completed. The report lists 8 detectors in the system and all 8 were tested. Sensitivity testing was completed on 04/21/2025 for the 8 duct detectors. No specific residents were affected by this alleged deficient practice. 2. How will you identify other residents having potential to be affected by the same deficient practice and what corrective action will be taken. No residents affected by the alleged deficient practice. On 04/21/25 the Maintenance Director/designee completed an audit of smoke detectors and duct detectors to ensure documentation in place for completion of biennial smoke detector sensitivity testing and annual duct detector differential testing; no other concerns identified. 3. What measures will be put into place or what systematic changes will you make to ensure that the deficient practice does not recur. The Maintenance Director was educated on 04/17/2025 related to maintaining documentation of the Fire Alarm System in accordance with National Fire Protection Association (NFPA) 101 by the Administrator. 4. How the corrective actions will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put into place. Random audits will be completed by the NHA/designee of smoke detectors and duct detectors to ensure documentation in place for completion of biennial smoke detector sensitivity testing and duct detector differential testing once a week for 4 weeks and then monthly for 2 months. Findings and audits will be reported to the QAPI committee for follow-up and recommendations monthly.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Failure to Perform and Document Annual Duct Detector Differential Testing
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Properly Test Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and properly test multiple fire alarm system components, including smoke detectors near the medical supply area and house laundry that could not be located, elevator fire hat and primary recall functions that could not be reset due to lack of a key, and an untested elevator control shunt trip. On revisit, the missing smoke detectors had been replaced with battery-operated units that were not connected to the building’s fire alarm notification system, and the previously identified fire alarm issues remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Fire Alarm System Inspection and Testing Documentation
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain required inspection and testing documentation for its fire alarm system. During surveyor review, no records could be produced to show that semi-annual visual inspections or the two-year smoke detector sensitivity testing had been completed, and the maintenance supervisor confirmed that this documentation was unavailable at the time of the survey. This deficiency affected the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Fire Alarm Documentation and Testing Records
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain required fire alarm system documentation and testing records. During record review with the Maintenance Director, there was no vendor-signed log book at the fire panel documenting work performed at each visit, no documentation of biennial smoke detector sensitivity testing, and no fire alarm system design plans located at the fire panel, as required by NFPA 101 and NFPA 72.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Proper Working Order
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors identified that the facility did not maintain its fire alarm system in accordance with NFPA 72 when the fire alarm control panel was observed displaying a trouble signal. During the observation, the Maintenance Director confirmed that the trouble condition was related to a faulty heat detector. This unresolved trouble indication showed that the fire alarm system was not being properly maintained to ensure it functioned as designed for the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Florida

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Florida — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙