K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
E

Smoke Barrier Wall Deficiencies on Second Floor

Fox Run At Orchard ParkOrchard Park, New York Survey Completed on 03-07-2025

Summary

During a Life Safety Code survey, it was observed that smoke barrier walls on the second floor of the facility were not properly maintained. Specifically, the smoke barrier walls were incomplete from floor to ceiling/roof deck, lacked a 30-minute fire resistance rating, and had open and unsealed penetrations that could allow the passage of smoke. One instance involved a piece of damaged drywall outside Resident Room 422, which was hanging loosely and required securing and re-caulking with fire-rated caulk. Another instance was found outside the Director of Nursing's Office, where a one-inch square penetration with a blue wire passing through it was observed. The Director of Facilities acknowledged the issues and noted that regular smoke barrier audits were not currently performed, although they had been conducted in the past during a construction project.

Plan Of Correction

Plan of Correction: Approved March 28, 2025 K372 Subdivision of Building Spaces – Smoke Barrier Construction 1. Corrective Action a. The Maintenance Department immediately secured the drywall piece and sealed the penetration using fire caulk in the smoke barrier outside of room 422 and sealed the penetration through the smoke barrier outside of the Director of Nursing’s office using fire caulk. b. Maintenance Staff were inserviced on inspection and maintenance of smoke barriers. 2. Identification of other smoke barriers having the potential to be affected The Director of Facilities and Maintenance Staff conducted a 100% audit of smoke barriers to ensure there were not any unsealed penetrations. 3. Systematic Changes The Director of Facilities and/or Maintenance Staff will conduct monthly audits of smoke barriers to ensure compliance. 4. Monitor Performance The Director of Facilities/designee will monitor monthly smoke barrier audits for 12 months. All audits will be reviewed quarterly at QA/QAPI meeting, and need for continuance after 12 months. 5. The Director of Facilities will be responsible for overall completion of the plan with respect to K372.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetrations in Smoke/Fire Barriers After Electrical Work
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire barriers in three of fourteen smoke compartments, including the hot water room, the barrier between the kitchen and a smoke compartment, and the smoke wall leading to the Alzheimer’s unit, had penetrations that were not properly fire-stopped. During the on-site interview, the Maintenance Director acknowledged that recent electrical work had been completed and that the contractor failed to seal these penetrations, resulting in noncompliance with NFPA 101 smoke barrier construction requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

A deficiency was identified when an unsealed penetration around data wires was observed in a smoke barrier wall on the second floor near the Rehabilitation Department. This issue was confirmed by the Administrator and Maintenance Director and affected one of two floors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unprotected Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

An unprotected penetration was found in a smoke barrier wall above double doors near the ADON/Medical Records Office, where blue and red wires passed through without proper protection. This issue, confirmed by the Director of Maintenance, affected two of twelve smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙