K0281 K281: Install proper backup exit lighting.
D

Deficiency in Egress Illumination

New Gouverneur Hospital S N FNew York, New York Survey Completed on 12-31-2024

Summary

During a Life Safety Code recertification survey, it was observed that the facility failed to ensure proper illumination of the means of egress in accordance with NFPA 101 standards. Specifically, on the basement level, the emergency exit discharge located by the Dry Storage Room and the exit leading to the loading dock were both found to be without light fixtures above the doors. Additionally, there were no light fixtures along the path leading to a public way, compromising the continuity of the egress path. These observations were made between 9:30 AM and 2:00 PM, and the findings were acknowledged by the Chief Executive Officer and the Director of Maintenance present during the survey.

Plan Of Correction

Plan of Correction: Approved February 3, 2025 K281 Illumination of Means of Egress 1. What Corrective Action(s) will be accomplished for those residents found to have been affected by the deficient practice Light fixtures were installed above the emergency exit discharge. Light fixtures were installed above the emergency exit discharge located by the Dry Storage Room on the basement level. Light fixtures were installed above the emergency exit discharge leading to the loading dock on the basement level. Additional light fixtures were installed along the path leading to a public way to ensure continuity in the path of egress. 2. How will you identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken The following corrective actions will be implemented to identify other residents who may be affected by the same practice: all areas of egress were assessed to ensure proper illumination is in place. 3. What measures will be put in place or what systemic changes you will make to ensure that the deficient practice does not recur Hospital Police will add inspection of proper illumination of the means of egress to daily building rounds. Hospital Police has been educated on this new responsibility, on confirming illumination of egress. Regular maintenance checks will be conducted to ensure that all light fixtures are functioning properly and that the means of egress remain illuminated in accordance with NFPA 101. All maintenance staff were in-serviced regarding illumination of means of egress. 4. How the Corrective Action(s) will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put into practice All egress areas will be monitored for proper illumination and functionality of the light fixtures monthly for a period of 3 months or until compliance is achieved. The results from the monitoring will be reported to the QAPI Committee. 5. Responsible Individual: Director of Maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0281 citations
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the Rehab corridor, as required by NFPA 101 standards. During a survey, it was found that turning off the wall-mounted light switches extinguished all lights in the corridor leading to an emergency stairwell exit. The Director of Maintenance confirmed the issue, noting that the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Illuminate Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not provide proper illumination for egress pathways, as required by NFPA 101. Observations revealed that exit doors from the French Quarter wing, the main entrance, and the Spanish Villa wing lacked necessary lighting for safe egress during darkness. These findings were confirmed by the Maintenance Director and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Illumination of Egress Pathways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

A Life Safety Code Survey found that the facility did not ensure proper illumination of egress pathways for four of seven exits. Observations revealed a lack of exterior lighting on several sections of the pathways. The Environmental Services Director was unaware of the deficiency but acknowledged the need for additional lighting.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Ensure Continuous Illumination in Egress Pathway
D
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination in the means of egress as required by NFPA 101. During a survey, it was found that turning off the wall-mounted light switches in the fifth-floor dining room also turned off all lights, including those needed for an emergency stairwell exit. This issue was identified on one of the three resident floors, and the Director of Maintenance confirmed the lights would be continuous.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Continuous Egress Illumination
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility did not maintain continuous illumination of the means of egress in one of five stair towers. Light fixtures failed to illuminate the exit by Component 1, as observed and confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illumination in Exit Stairways
E
K0281 K281: Install proper backup exit lighting.
Short Summary

The facility failed to maintain proper illumination in the exit stairways, affecting one of three floors. An observation revealed that the lights in the first floor South main stair tower were not illuminating. This was confirmed during an exit interview with the Administrator and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙