K0351 K351: Install an approved automatic sprinkler system.
E

Deficiencies in Sprinkler System Installation and Maintenance

Hillside Manor Rehab & Extended Care CenterJamaica Estates, New York Survey Completed on 03-31-2025

Summary

The facility failed to ensure that all components of the building's extinguishing system were installed in accordance with NFPA 101 standards. During the Life Safety Code Recertification survey, several deficiencies were observed. In the A/C No. 10 room, a sidewall sprinkler was improperly installed facing downwards, parallel to the wall instead of having the deflector parallel to the ceiling. Additionally, a concealed sprinkler in the 1st Floor corridor by the Conference Room was missing its cap. The Loading Dock area lacked sprinkler coverage from the door to the 5 steps. Furthermore, in the small conference room on the 1st Floor, a sprinkler head was missing an escutcheon and a 2 ft by 2 ft ceiling tile. Missing escutcheons and broken ceiling tiles were observed throughout the facility, indicating a widespread issue with the maintenance of the sprinkler system.

Plan Of Correction

Plan of Correction: Approved April 26, 2025 I. Immediate Corrective Action 1) The Director of Engineering contacted the fire sprinkler company upon discovery to correct the following: a) Reinstall in the correct position a sidewall sprinkler in the A/C No. 10 room b) On 04/25/2025 the 1st Floor corridor by the Conference Room, a concealed sprinkler that had the missing cap was replaced c) Fire sprinkler company contacted to install the loading dock area sprinkler coverage from the door to the 5 steps d) On 4/25/2025, in the small conference room, on the 1st Floor, the observed sprinkler head that was missing an escutcheon and ceiling tile was installed. 2) The facility engineer in conjunction with the sprinkler company reviewed all sprinklers for proper escutcheon plates and replaced any that were found to be missing. 3) The facility engineer replaced all damaged ceiling tiles to ensure proper fitting. II. Identification of Other Residents 1) The facility respectfully states that no residents were involved in this deficiency, however all residents were indirectly affected. 2) The Director of Engineering reviewed sprinkler coverage throughout, and no additional areas were affected. III. Systemic Changes 1) The Administrator, in conjunction with the Director of Engineering, reviewed and revised the facility sprinkler inspection policies and procedures and incorporated the requirements of sprinkler coverage as per NFPA 13 and NFPA 99 into the policies. 2) Any plans which are implemented shall include a review of fire sprinkler coverage by an approved licensed individual. 3) All Maintenance staff will be informed and educated regarding sprinkler heads that were installed and their location, as well as an overview of requirements for sprinkler coverage as per K351. 4) The education will concentrate on the requirements to maintain sprinklers in all needed areas as well as ensure sprinkler heads are installed as required with all associated hardware. 5) A copy of the attendance will be maintained for reference and validation. IV. QA Monitoring 1) The Administrator, in conjunction with the Director of Maintenance, will conduct monthly reviews and inspections of sprinkler reports for the next 3 months, then upon completion of work thereafter. Documentation will be maintained in a logbook for reference and validation. 2) The Director of Maintenance will review the findings and report to the QA Committee on a quarterly basis, for evaluation by the QA Committee. V. Responsible Person: Director of Engineering/Administrator/designee

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler System Installation in Electrical Room
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to install an automatic sprinkler system in the Main electrical (switchgear) Room in the basement, affecting one of three levels. This deficiency was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations, indicating incomplete sprinkler protection as per NFPA standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙