K0363 K363: Install corridor and hallway doors that block smoke.
E

Failure to Maintain Corridor Door Latching

Chestnut Hill Rehabilitation And Healthcare CenterWilkes Barre, Pennsylvania Survey Completed on 04-08-2025

Summary

The facility failed to maintain three corridor openings, which affected two of the three floors. During an observation on April 8, 2025, several deficiencies were noted. At 11:27 am, the door to the Dietary, Food Service Room required adjustment to fully latch into the frame. This indicates that the door was not properly aligned or maintained to ensure it could close securely, potentially compromising the safety and smoke resistance of the corridor. Further observations revealed additional issues on the 2nd floor. At 12:24 pm, the Personal Laundry Room door failed to latch into the frame because the strike plate was taped over, preventing the door from securing properly. Additionally, at 12:32 pm, the door to Resident Room 202 in the Aspen area also failed to latch into the frame. These deficiencies were confirmed during an exit interview with the Facility Administrator and Facilities Manager, highlighting a lapse in maintaining the integrity of corridor doors as required by regulations.

Plan Of Correction

1. The food service door latch has been adjusted to ensure latching; the Personal Laundry Room door latch has been replaced, Aspen Resident Room 202 latch has been adjusted to ensure latching. 2. Dietary doors will be checked to ensure they latch into their frame. Resident room doors in Aspen will be checked to ensure they latch into their frames. 3. NHA/Designee will in-service Maintenance Director on assuring self-closure doors latch correctly. 4. Maintenance/Designee will audit weekly x4, then monthly x3. Audits will be reported to QAPI, for further recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0363 citations
Failure of Corridor Door to Latch Properly
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that a corridor door to a resident room on one floor failed to latch into the frame when tested, meaning it did not meet NFPA 101 requirements for positive latching of corridor doors. The Facilities Manager and Facility Life Safety staff confirmed during interview that this corridor door did not latch properly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Multiple Corridor Door Deficiencies Impacting Smoke and Fire Protection
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors identified several corridor door deficiencies, including doors that failed to latch, lacked smoke tight integrity, and had missing locksets, across multiple floors. These issues were confirmed by facility leadership during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Properly Latching Corridor Doors
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two corridor doors, one on the third floor and one on the second floor, did not latch when tested, affecting two smoke compartments. The Facility Administrator and Maintenance Director confirmed these deficiencies, which were not in compliance with fire and smoke protection requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Positive Latching of Corridor Door
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

A corridor door leading to the Patio Lounge failed to positively latch within the door frame, as observed and confirmed by the Director of Maintenance. This deficiency affected one of twelve smoke compartments and did not meet NFPA 101 and CMS requirements for corridor door latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Corridor Doors for Smoke Resistance and Latching
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that corridor doors to two resident rooms did not close and latch properly, as confirmed by the facility's Administrator and Maintenance Director. This deficiency affected one of five smoke compartments and did not meet regulatory requirements for smoke resistance and positive latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Corridor Doors Blocked Open with Wedges
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two resident rooms had wooden door wedges holding corridor doors open, preventing them from closing as required for fire safety. Facility staff confirmed that the wedges impeded proper door closure.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙