K0352 K352: Properly install and monitor supervisory attachments on automatic sprinkler systems.
F

Failure to Maintain Automatic Sprinkler System

Chestnut Hill Rehabilitation And Healthcare CenterWilkes Barre, Pennsylvania Survey Completed on 04-08-2025

Summary

The facility failed to maintain the automatic sprinkler system as required, which was evidenced by a supervisory signal indicating a fire pump loss of power on the fire alarm panel. This issue was observed during an inspection on April 8, 2025, affecting all three floors of the facility. Although the facility had a new fire pump on site, it had not yet been installed. Previous fire alarm testing conducted on April 1, 2025, did not reveal any deficiencies. The deficiency was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

Plan Of Correction

1. The facility has contracted with Beach Lake Sprinkler to replace the fire pump panel on the week of May 5, 2025. 2. The facility fire pump controller will be reviewed and updated as needed. 3. NHA will educate the Maintenance Director, to assure the fire pump is updated as needed. 4. Fire pump will be audited weekly x4 then monthly x3 by Maintenance Director/Designee to ensure fire alarm pump is up to date. Audits will be reviewed at QAPI for further recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0352 citations
Deficiency in Sprinkler System Supervisory Signal Monitoring
F
K0352 K352: Properly install and monitor supervisory attachments on automatic sprinkler systems.
Short Summary

The facility did not ensure that automatic sprinkler system supervisory attachments were properly installed and monitored, as the system was found capped and failed inspection, with supervisory or trouble alarms present on the fire alarm control panel indicating part of the system was shut down.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsupervised Sprinkler System Valves
F
K0352 K352: Properly install and monitor supervisory attachments on automatic sprinkler systems.
Short Summary

The facility's sprinkler system was found to have two unsupervised outside screw and yoke (OS&Y) valves, which could prevent staff from knowing if the system was impaired. The domestic and sprinkler riser water line shared the same main water line from the city, and the main water riser room was located in a corporate office storage room. This deficiency had the potential to affect 88 residents.

Inspection fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙