F0908 F908: Keep all essential equipment working safely.
D

Facility Fails to Repair A/C Unit and Maintain Resident Rooms

Concordia ManorSaint Petersburg, Florida Survey Completed on 03-07-2025

Summary

The facility failed to ensure timely repairs for one of three air conditioning units, which had been non-functional for approximately one month. The Director of Maintenance (DOM) identified the malfunction on 01/28/2025, and a proposal for repairs was submitted, but as of 03/07/2025, the repairs had not been completed despite approval of the purchase requisition on 02/12/2025. The facility relied on a portable unit in the interim, but no further information was provided regarding the timeline for the repair of the air conditioning unit. Additionally, the facility did not maintain resident rooms in a safe and sanitary manner, as evidenced by observations of cracking, peeling, and dislodged ceiling material with discoloration in two resident rooms. Room 104, which was unoccupied, had three areas of dislodged paint, each approximately 2 feet by 3 feet. Room 105, which housed four residents, had similar issues with cracks and discolored paint material approximately 2 feet by 2 feet. The Nursing Home Administrator (NHA) confirmed the air conditioning unit had not been fixed but did not comment on the condition of the resident rooms.

Plan Of Correction

This plan of correction is submitted as required under state and federal laws. The submission of this plan of correction does not constitute an admission on the part of the skilled nursing facility as to the accuracy of the surveyor's findings or the conclusion drawn there from. The plan of correction does not constitute a deficiency or that the scope and severity regarding any of the deficiencies cited are correctly applied. Any changes to facility policy and procedures should be considered remedial measures as that concept is employed in rule 407 of the federal rules of evidence and should be inadmissible in any proceeding on that basis. The facility submits this plan of correction with the intention that it be inadmissible by any third party in any civil or criminal action against the facility or any employee, agent, officer, director, or shareholders of the facility. The facility has not waived any rights to contest any of these allegations or any allegation or action. F-0908 Essential Equipment, Safe Operating Condition Element #1. The facility's air conditioning unit was repaired on, Ceiling in resident are scheduled for repair on. Element #2. The facility's remaining air conditioning units were inspected for proper functioning on and no concerns were identified. Resident room ceilings were inspected for cracked and/or peeling paint on No areas of noncompliance were identified. Element #3. Nursing Home Administrator (NHA) and/or Designee in-serviced Concierge personnel and facility staff regarding the identification and reporting of any areas of disrepair or noncompliance of the physical environment in resident rooms. Nursing Home Administrator (NHA) in-serviced Maintenance Director regarding the Physical Environment Policy. Regional Director of Operations Consultant in-serviced the Nursing Home Administrator (NHA) regarding management of product or equipment requisitions. Element #4. Nursing Home Administrator (NHA) will randomly audit resident room ceilings and air conditioning units five (5) times weekly times eight (8) weeks to ensure that ceilings do not have cracked/peeling paint and that air conditioning units are properly functioning. Completed audits will be brought to the stand up meetings and reviewed by the Interdisciplinary Team (IDT). Results of the audits will be brought by the Nursing Home Administrator (NHA) or Director of Nursing (DON) and discussed at monthly Quality Assurance Performance Improvement meetings for review and recommendation. Element #5: Facility's Allegation of Compliance Date is.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Kitchen Dishwashing System Leak Not Maintained
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep a kitchen dishwashing system in good working order when surveyors observed water flowing from a metal device under the counter, with buckled tile and peeled-back wall trim nearby. A kitchen staff member said maintenance had known about the leak for about a month, and maintenance later confirmed the issue had not been reported through the TELS system and that the damage was not new.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lint Buildup in Dryer Lint Trap
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Lint Buildup in Dryer Lint Trap: One of two dryers was observed running with lint buildup in the lint trap after the lint door was opened during a laundry tour. The MSS stated the lint trap should be cleaned every 2 hours for fire safety, and an LA stated she forgot to clean Dryer 2's lint trap. Facility policy required laundry equipment to be maintained per manufacturer instructions and kept in a safe, operable condition.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Refrigeration Not Maintained in Working Condition
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Essential kitchen equipment was not kept in good working condition. A large kitchen refrigerator had standing water on the bottom shelf and water dripping from the top onto covered food, and a resident refrigerator freezer had heavy ice buildup with a splintered gasket that did not attach well. The ADON and Maintenance Director both verified the equipment problems, and the MD stated the refrigerator was not working properly and needed repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dishwasher Thermometer Inaccurate and Temperatures Below Required Level
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Dishwasher Thermometer Inaccurate and Temps Below Required Level: The low-temp dishwasher was observed with wash and rinse temps below the facility's required 120F minimum, and the DS stated staff had to handwash dishes while the machine was out of order. The MS later found the machine's thermometer was not reading accurately, with the manual thermometer showing 135.1F while the machine read 118F, and the DS said the length of time the thermometer had been inaccurate was unknown.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Safe Operating Condition
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in safe operating condition. A plate warmer was plugged in but only held room-temperature plates, and staff said it had not warmed plates since the prior week or earlier. A dishwasher temperature gauge was also faulty, reading 110F while a separate gauge showed the water was 122F during operation. The Maintenance Director said he had not been notified of either issue and found no June maintenance entries for the plate warmer or dishwasher gauge.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Working Order
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in proper working order, affecting nearly all residents who received meals from the kitchen. Surveyors observed significant ice buildup in two reach-in freezers, including on food products, and found the garbage disposal covered. Dietary staff said the disposal had been broken for about a year, and the DM reported the freezers were constantly in defrost with possible door seal problems. Maintenance confirmed the disposal needed replacement and said approval was delayed because the facility was being sold.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Florida

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Florida — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.