K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
D

Deficient Lighting in Egress Path

Casa PromesaBronx, New York Survey Completed on 12-09-2024

Summary

The facility failed to ensure that the lighting in the path of egress was fully functional. During a life safety code survey, it was observed that the egress path in a stairwell leading to Anthony Avenue had two lighting tubes that were only partially illuminated. This issue was noted on one out of four units. The observation was made on two consecutive days, and the Maintenance Director was informed immediately after the finding.

Plan Of Correction

Plan of Correction: Approved December 19, 2024 Immediate Corrective Action: The Maintenance Director and Facilities Supervisor on 12.04.2024 effectively replaced the two identified lightbulbs/lighting tubes that were partially illuminated in stairwell egress to (NAME) Avenue - in accordance with NFPA 101 section 7.9. Identification of Others Potentially Affected: The facility respectfully submits all residents were potentially affected by this practice. System Changes to Prevent Recurrence: The Maintenance Director and facility team were re-in-serviced on 12.09.2024 for state requirements regarding Means of Egress and TAG K-291: Emergency Lighting specificities by the compliance officer. The Maintenance Director will continue to perform Monthly emergency Lights test - 30 seconds per month hold button; and annual checks of 90 minutes unplugged. In addition, the maintenance team are now required to observe, record and ensure the path of egress is functionally illuminated during daily environmental rounds. Quality Assurance Monitoring: The Maintenance Director will complete the updated daily compliance facilities testing tracker and immediately provide replacement or work order(s) for TAG K291 on the tracker in the event illumination is affected. The Internal Record of Inspection and Testing reports are then reviewed by the facilities Manager and the compliance team. Any deficient practice/findings will be reported for reconciliation during the QA monthly meetings. Responsible Party: Maintenance Director

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0291 citations
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Annual 90‑Minute Emergency Battery Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or could not document the required annual 90‑minute test of battery-powered emergency lighting as required by NFPA 101 (2012 and 2021). During a record review with the Maintenance Director, no records were available to show that the annual 90‑minute emergency lighting test had been completed, and the Maintenance Director acknowledged the absence of this documentation, resulting in a cited deficiency affecting all occupants of the building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility failed to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101. During record review with the Maintenance Director, no documentation was available for the monthly 30-second tests or the annual 90-minute tests for all sampled battery backup emergency lights. The Maintenance Director acknowledged the absence of these records, and the deficiency was determined to affect all residents and staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Emergency and Exit Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or document required monthly and annual inspections of battery back-up emergency and exit lighting in accordance with NFPA 101 standards. During record review, no evidence was available to show that emergency lights throughout the building had been tested for the required 90-minute annual duration, despite multiple requests for documentation. The Maintenance Director confirmed that the documentation could not be produced, and this deficiency potentially affected all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Emergency Lighting Testing
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not provide documentation to verify that required monthly and annual tests of battery-powered emergency lighting were performed, as confirmed by both document review and interviews with the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Emergency Lighting Test
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors determined that the facility did not conduct or document the required annual 90-minute test of battery backup emergency lighting. This was confirmed by facility leadership during the survey process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙