Inadequate Sprinkler System Coverage and Improper Use of Sprinkler Piping
Penalty
Summary
The facility failed to ensure that all areas of the nursing home were adequately protected by an automatic sprinkler system, as required by the 2012 NFPA 101 standards. During a life safety survey, it was observed that there was no sprinkler protection underneath stair D at the first-floor lowermost landing. Additionally, the atrium off the lobby had sprinklers installed above the windows on one side, but it was unclear if these provided sufficient coverage for the entire space, which measured approximately 30' by 40'. Furthermore, in the fire pump room, electrical BX cable was improperly suspended from the sprinkler piping, violating the standard that prohibits using sprinkler piping or hangers to support non-system components. These deficiencies were noted during the survey and discussed with the Administrator during the exit conference.
Plan Of Correction
Plan of Correction: Approved January 13, 2025 Element 1 Immediate Corrective Action: The facility immediately consulted a licensed fire protection vendor to add a head to provide sprinkler coverage under stairway D. The fire protection vendor conducted a thorough assessment to verify sprinkler head placements above the Atrium/Lobby windows. Additional sprinkler heads will be added every 7 feet to ensure necessary coverage for the entire space in the atrium. The BX cable suspended from sprinkler piping was immediately secured using appropriate non-piping support brackets to comply with NFPA 2012 101 19.3.5.1 requirements. All sprinkler piping in the facility was inspected to ensure no other electrical cables or utilities are improperly supported. The maintenance director visually inspected the entire facility; no other issues were identified. Element 2 Residents at Risk: While no residents were affected by this practice, the potential existed for residents to be affected by this deficient practice. Element 3 Systemic Changes: Maintenance and engineering staff were retrained on sprinkler system requirements including proper sprinkler head placement and coverage. Prohibition of using sprinkler pipes for utility support was emphasized. The facility's preventive maintenance program was updated to include a semi-annual review of sprinkler systems by our Life Safety Consultant from Ridgefield Associates. Maintenance logs will be reviewed by the maintenance director monthly to ensure compliance. Element 4 Monitoring: The maintenance director will conduct monthly inspections of sprinkler systems coverage and utility compliance. Quarterly audits of sprinkler systems will be conducted by an external fire protection contractor and Ridgefield Associates for the next 12 months. Audit results will be reported to the administrator for compliance; any negative findings will be corrected immediately. The maintenance director will report for the next 3 quarters the results of the inspections to the QAPI Committee. The QAPI Committee will determine if further action is required. Element 5 Person responsible: Maintenance Director