Stay Ahead of Compliance with Monthly Citation Updates


In your State Survey window and need a snapshot of your risks?

Survey Preparedness Report

One Time Fee
$79
  • Last 12 months of citation data in one tailored report
  • Pinpoint the tags driving penalties in facilities like yours
  • Jump to regulations and pathways used by surveyors
  • Access to your report within 2 hours of purchase
  • Easily share it with your team - no registration needed
Get Your Report Now →

Monthly citation updates straight to your inbox for ongoing preparation?

Monthly Citation Reports

$18.90 per month
  • Latest citation updates delivered monthly to your email
  • Citations organized by compliance areas
  • Shared automatically with your team, by area
  • Customizable for your state(s) of interest
  • Direct links to CMS documentation relevant parts
Learn more →

Save Hours of Work with AI-Powered Plan of Correction Writer


One-Time Fee

$49 per Plan of Correction
Volume discounts available – save up to 20%
  • Quickly search for approved POC from other facilities
  • Instant access
  • Intuitive interface
  • No recurring fees
  • Save hours of work
K0324
F

Deficiency in Commercial Cooking Hood Suppression System

Boca Raton, Florida Survey Completed on 02-04-2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Summary

The facility failed to maintain its commercial cooking facility in accordance with NFPA 101 standards. During a fire safety tour, it was observed that the seams of the kitchen's commercial cooking hood suppression system were not sealed or made greasetight. This deficiency was identified during an inspection conducted on February 4, 2025, at 11:09 AM, with the Maintenance Director present. The Maintenance Director acknowledged the findings during an interview conducted concurrently with the observations. The issue was further reviewed with the Administrator, the Regional Maintenance Director, and the Maintenance Director during the exit conference on the same day at 2:40 PM. The report cites specific sections of NFPA 96 and NFPA 101 that were not adhered to, indicating a failure to comply with the required fire safety standards for commercial cooking operations.

Plan Of Correction

Corrective Actions The facility's kitchen hood seams were sealed to ensure that the kitchen hood was grease tight on 2/5/2025. Identification of Others Potentially Affected The facility only has one kitchen hood, so no further evaluations are needed. Systemic Changes The Maintenance Director, or designee, will continue to perform documented monthly inspections of the facility's kitchen hood to ensure the kitchen hood seams remain sealed and grease tight on an ongoing basis as part of the facility's life safety program. Quality Assurance Results of the monthly kitchen hood inspections will be presented at the monthly QA meetings for 3 months. If substantial compliance is not met after 3 months, results of the ongoing monthly inspections will be brought to QA meetings until substantial compliance is met.