F0908 F908: Keep all essential equipment working safely.
E

Heating System Deficiency in LTC Facility

Ross Center For Nursing And RehabilitationBrentwood, New York Survey Completed on 01-17-2025

Summary

The facility failed to maintain its heating system in proper working condition, resulting in temperatures in resident rooms, shower rooms, and common areas falling below the required range. Observations revealed that the hot water coil heating system in several resident rooms and a shower room was not delivering heat, and portable heating units were in use in some resident rooms. Additionally, three out of four resident shower rooms lacked any type of heating system, and residents' room windows were not properly maintained to prevent air drafts. The Director of Maintenance (DOM) was unaware of the temperature issues and stated that they did not receive any complaints from residents or staff. The DOM admitted that air temperatures were not taken daily, and there was no regular maintenance schedule in place. Environmental rounds were conducted once per month without documentation, and the facility did not have a temperature policy. The heating system had not been changed since 2013, and residents could control the heating coil units and open windows themselves. The facility's policy named Cold Weather Emergency was updated, but it did not specify how temperatures should be taken and documented. The DOM stated that repairs would be done in-house, and a plumbing company was scheduled to check the heating system. However, no maintenance records were provided to indicate regular inspection and maintenance of the facility's heating system for all three nursing units. The lack of a systematic approach to maintaining the heating system and addressing air drafts contributed to the deficiency.

Plan Of Correction

Plan of Correction: Approved February 17, 2025 i. Residents rooms that were below 70 were immediately offered a room change. i.a The Administrator and Director of Maintenance in consultation with plumber/boiler vendor did a complete assessment of the heating system and identified multiple issues. 1. Hallway thermostat schedule wasn't set properly. 2. Visitor Bathroom heater was defective. 3. One boiler would go into standby mode. 4. Some windows needed to be resealed. 5. Some rooms were missing insulation above the windows. 6. Some of the vents on the room units were in the open position. 7. Some units fan blower motors need to be replaced. 8. East Shower room, one West shower room didn't have heating units. 9. One west shower room, North shower room heating unit weren't working. i.b 1. Hallway thermostat was reprogrammed, a lock box was replaced with access restricted to maintenance. 2. Visitor Bathroom heater was replaced, staff bathroom repaired. 3. Computer control board on the boiler was replaced. 4. Windows were resealed. 5. Insulation above the windows was replaced. 6. All vents were checked and closed. 7. All blower motors were checked and those that were broken were replaced. 8. A ductless unit was installed in the East Shower room, A ductless unit was installed in the West shower room. 9. West shower room heating unit was repaired, A ductless unit was installed in the North shower room. ii. This deficiency has the potential to affect all residents in the facility. iii. Policy & Procedure for Heating system was created and maintenance staff inserviced on new policy. iv. An audit tool will be developed to ensure that the heating system is functioning properly and a daily room temperature log will be added to the daily room check log. Any negative findings during monitoring will be addressed by the Maintenance Director or designee and referred to the QAPI committee for further review. Audits will be conducted weekly x 4 weeks, then monthly x 3 months. v. Director of Maintenance/designee will be responsible for F908 tag.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Kitchen Dishwashing System Leak Not Maintained
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep a kitchen dishwashing system in good working order when surveyors observed water flowing from a metal device under the counter, with buckled tile and peeled-back wall trim nearby. A kitchen staff member said maintenance had known about the leak for about a month, and maintenance later confirmed the issue had not been reported through the TELS system and that the damage was not new.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lint Buildup in Dryer Lint Trap
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Lint Buildup in Dryer Lint Trap: One of two dryers was observed running with lint buildup in the lint trap after the lint door was opened during a laundry tour. The MSS stated the lint trap should be cleaned every 2 hours for fire safety, and an LA stated she forgot to clean Dryer 2's lint trap. Facility policy required laundry equipment to be maintained per manufacturer instructions and kept in a safe, operable condition.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Refrigeration Not Maintained in Working Condition
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Essential kitchen equipment was not kept in good working condition. A large kitchen refrigerator had standing water on the bottom shelf and water dripping from the top onto covered food, and a resident refrigerator freezer had heavy ice buildup with a splintered gasket that did not attach well. The ADON and Maintenance Director both verified the equipment problems, and the MD stated the refrigerator was not working properly and needed repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dishwasher Thermometer Inaccurate and Temperatures Below Required Level
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Dishwasher Thermometer Inaccurate and Temps Below Required Level: The low-temp dishwasher was observed with wash and rinse temps below the facility's required 120F minimum, and the DS stated staff had to handwash dishes while the machine was out of order. The MS later found the machine's thermometer was not reading accurately, with the manual thermometer showing 135.1F while the machine read 118F, and the DS said the length of time the thermometer had been inaccurate was unknown.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Safe Operating Condition
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in safe operating condition. A plate warmer was plugged in but only held room-temperature plates, and staff said it had not warmed plates since the prior week or earlier. A dishwasher temperature gauge was also faulty, reading 110F while a separate gauge showed the water was 122F during operation. The Maintenance Director said he had not been notified of either issue and found no June maintenance entries for the plate warmer or dishwasher gauge.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Equipment Not Maintained in Working Order
F
F0908 F908: Keep all essential equipment working safely.
Short Summary

Kitchen equipment was not maintained in proper working order, affecting nearly all residents who received meals from the kitchen. Surveyors observed significant ice buildup in two reach-in freezers, including on food products, and found the garbage disposal covered. Dietary staff said the disposal had been broken for about a year, and the DM reported the freezers were constantly in defrost with possible door seal problems. Maintenance confirmed the disposal needed replacement and said approval was delayed because the facility was being sold.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙

Connection lost — reconnecting… We couldn't reconnect automatically. Please reload the page to continue.