F0908 F908: Keep all essential equipment working safely.
E

Heating System Deficiency in LTC Facility

Ross Center For Nursing And RehabilitationBrentwood, New York Survey Completed on 01-17-2025

Summary

The facility failed to maintain its heating system in proper working condition, resulting in temperatures in resident rooms, shower rooms, and common areas falling below the required range. Observations revealed that the hot water coil heating system in several resident rooms and a shower room was not delivering heat, and portable heating units were in use in some resident rooms. Additionally, three out of four resident shower rooms lacked any type of heating system, and residents' room windows were not properly maintained to prevent air drafts. The Director of Maintenance (DOM) was unaware of the temperature issues and stated that they did not receive any complaints from residents or staff. The DOM admitted that air temperatures were not taken daily, and there was no regular maintenance schedule in place. Environmental rounds were conducted once per month without documentation, and the facility did not have a temperature policy. The heating system had not been changed since 2013, and residents could control the heating coil units and open windows themselves. The facility's policy named Cold Weather Emergency was updated, but it did not specify how temperatures should be taken and documented. The DOM stated that repairs would be done in-house, and a plumbing company was scheduled to check the heating system. However, no maintenance records were provided to indicate regular inspection and maintenance of the facility's heating system for all three nursing units. The lack of a systematic approach to maintaining the heating system and addressing air drafts contributed to the deficiency.

Plan Of Correction

Plan of Correction: Approved February 17, 2025 i. Residents rooms that were below 70 were immediately offered a room change. i.a The Administrator and Director of Maintenance in consultation with plumber/boiler vendor did a complete assessment of the heating system and identified multiple issues. 1. Hallway thermostat schedule wasn't set properly. 2. Visitor Bathroom heater was defective. 3. One boiler would go into standby mode. 4. Some windows needed to be resealed. 5. Some rooms were missing insulation above the windows. 6. Some of the vents on the room units were in the open position. 7. Some units fan blower motors need to be replaced. 8. East Shower room, one West shower room didn't have heating units. 9. One west shower room, North shower room heating unit weren't working. i.b 1. Hallway thermostat was reprogrammed, a lock box was replaced with access restricted to maintenance. 2. Visitor Bathroom heater was replaced, staff bathroom repaired. 3. Computer control board on the boiler was replaced. 4. Windows were resealed. 5. Insulation above the windows was replaced. 6. All vents were checked and closed. 7. All blower motors were checked and those that were broken were replaced. 8. A ductless unit was installed in the East Shower room, A ductless unit was installed in the West shower room. 9. West shower room heating unit was repaired, A ductless unit was installed in the North shower room. ii. This deficiency has the potential to affect all residents in the facility. iii. Policy & Procedure for Heating system was created and maintenance staff inserviced on new policy. iv. An audit tool will be developed to ensure that the heating system is functioning properly and a daily room temperature log will be added to the daily room check log. Any negative findings during monitoring will be addressed by the Maintenance Director or designee and referred to the QAPI committee for further review. Audits will be conducted weekly x 4 weeks, then monthly x 3 months. v. Director of Maintenance/designee will be responsible for F908 tag.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Expired Supplies Found in Crash Carts
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Expired supplies were found in two crash carts on nursing units 1B and 2B. An opened Ambu bag in the 2B cart was expired, and the 1B cart contained two expired Ambu bags and expired Assure Prism glucometer strips. RN staff confirmed the items were expired and should not have been in the carts.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Stove Burner Not Functioning
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

A gas stove in the kitchen had a back center burner that would not ignite when turned on, and staff reported it had been not working for about 1 to 2 months. Interviews showed cooks were expected to report equipment problems to the DM, who would notify Maintenance, but the issue was not promptly communicated to Maintenance. No gas odor or hissing was observed, and the burner was later taken out of service until repaired.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Elevator Malfunctioned and Remained in Need of Repair
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

The facility failed to keep one of its elevators in safe operating condition. Records showed elevator two malfunctioned multiple times and needed a replacement part, and residents and staff were aware of the repeated malfunctions. The Administrator confirmed the elevator was malfunctioning and needed repair.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Dryer Lint Traps
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Failure to Maintain Dryer Lint Traps: Surveyors observed heavy lint buildup in both dryer lint traps, with lint hanging from each trap and covering the full trap surface. The sign-off log showed no entries after the prior shift, and staff interviews confirmed the required two-hour checks and documentation were not consistently completed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Glucometer Calibration and Quality Control Not Documented
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Glucometer calibration and QC were not documented for one glucometer on Medication Cart D, and the QC log was blank for the scheduled check. LVN and DON verified that the 11-7 shift was responsible for nightly/daily calibration and QC to support accurate blood sugar readings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Thermostats Not Powered On or Working
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Thermostats Not Powered On or Working: Two of five sampled thermostats were observed turned off with black screens and no visible power. A resident’s RP said it was always hot in the resident’s room and a fan was provided because there was no working AC. The MS stated the thermostats should be on and working to regulate room temperatures, but he was unsure how often they should be checked.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release October 8, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report