E

Obstructed Emergency Exit Egress Paths

Neshaminy Manor HomeWarrington, Pennsylvania Survey Completed on 01-30-2025

Summary

The facility failed to maintain the means of egress free of impediments, as observed during a survey. On January 30, 2025, at 11:20 a.m., it was noted that emergency exit egress paths to the public way were obstructed by snow and ice. This issue affected two of the three levels of the facility. Specific locations of the obstructions included the AO courtyard emergency exit at 10:10 a.m. and the D1 patio at 11:10 a.m. The obstructions were confirmed during an exit interview with the Administrator and Maintenance Director on the same day at 12:45 p.m.

Plan Of Correction

The snow and ice were removed from the emergency exit egress paths for the A0 courtyard emergency exit and the D1 patio. Maintenance director or designee to conduct inspection of the emergency exit egress paths for the A0 courtyard and D1 patio to ensure they are not obstructed by snow and ice after winter storms. The Maintenance Director or designee will report monthly findings to Quality Assurance for a 90-day period.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0211 citations
Staff Inability to Operate Locked Smoking Patio Exit Gate
E
K0211
Short Summary

Surveyors found that staff assigned to the designated smoking patio did not have the necessary knowledge to operate the electronic magnetic locked exit gate leading to the public way. During a fire safety tour, a CNA serving as the Smoking Area Attendant repeatedly entered the correct access code but could not open the gate because she pulled instead of pushed, demonstrating that staff were not fully able to utilize this means of egress as required by NFPA 101. The Administrator and Maintenance Director confirmed these observations, and the deficiency was noted as affecting residents who smoke.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Means of Egress Obstructed by Two-Step Lock on Office Door
C
K0211
Short Summary

A two-step lock, including a dead bolt, was observed on the environmental services office door next to the salon, potentially impeding emergency egress. This was confirmed by the administrator and maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 'Not an Exit' Signage on Courtyard Door
E
K0211
Short Summary

A door leading to an enclosed courtyard in the Ivy Wing South Living Room was observed without a 'Not an Exit' sign, making it possible to mistake the door for an exit. This lack of signage was confirmed by facility leadership and resulted in noncompliance with NFPA 101 requirements for maintaining clear means of egress.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Headroom in Basement Corridor
B
K0211
Short Summary

Surveyors observed that the headroom in a basement corridor was approximately 6 feet 2 inches, which is below the required 6 feet 8 inches for means of egress. This was confirmed by the Administrator and affected one of two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Emergency Exit Due to Chained Patio Gate
F
K0211
Short Summary

A gate leading from the patio area was found chained shut, blocking a designated emergency exit. This obstruction was observed and confirmed by the Maintenance Director, preventing proper egress in case of emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed and Inaccessible Emergency Exits Identified
E
K0211
Short Summary

Surveyors found that multiple emergency exits were inaccessible or obstructed, including a sealed exterior door, a corridor blocked by dialysis transport chairs, and a stuck exit door from the main dining room. These issues were confirmed by the maintenance director during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙