K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
D

Emergency Lighting Deficiency in Laundry Room

Longwood At OakmontVerona, Pennsylvania Survey Completed on 01-08-2025

Summary

The facility failed to maintain emergency lighting in operable condition, as observed during an inspection. Specifically, an emergency light located above the dryers in the laundry room was found to be damaged and missing parts. This deficiency was confirmed during an exit interview with the Facility Administrator and Maintenance Director.

Plan Of Correction

The facility submits this plan of correction under procedures established by the Department of Health in order to comply with the Department's directive to change conditions which the Department alleges are deficient under State and Federal regulations relating to long term care. This plan of correction should not be construed as either a waiver of the Facility's right to appeal and to challenge the accuracy or severity of the alleged deficiencies or an admission of past or ongoing violations of State and Federal regulatory requirements. The emergency light for dryer side of the laundry was replaced on 1/14/2025. The maintenance director/designee will complete a review by January 17 of all emergency lights. Any identified emergency lights found to not be operational will be addressed at time of discovery. The maintenance team will be re-educated by the maintenance director on the need to test all emergency lights and report any issues with proper function immediately upon discovery. The emergency lights are on a monthly service check and an annual 90-minute test. The maintenance director/designee will submit results of the audits to the Quality Assurance Performance Improvement Committee for the next two quarters. Any identified negative trends will be addressed by the committee for further follow up.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0291 citations
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Annual 90‑Minute Emergency Battery Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or could not document the required annual 90‑minute test of battery-powered emergency lighting as required by NFPA 101 (2012 and 2021). During a record review with the Maintenance Director, no records were available to show that the annual 90‑minute emergency lighting test had been completed, and the Maintenance Director acknowledged the absence of this documentation, resulting in a cited deficiency affecting all occupants of the building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility failed to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101. During record review with the Maintenance Director, no documentation was available for the monthly 30-second tests or the annual 90-minute tests for all sampled battery backup emergency lights. The Maintenance Director acknowledged the absence of these records, and the deficiency was determined to affect all residents and staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Emergency and Exit Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or document required monthly and annual inspections of battery back-up emergency and exit lighting in accordance with NFPA 101 standards. During record review, no evidence was available to show that emergency lights throughout the building had been tested for the required 90-minute annual duration, despite multiple requests for documentation. The Maintenance Director confirmed that the documentation could not be produced, and this deficiency potentially affected all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Emergency Lighting Testing
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not provide documentation to verify that required monthly and annual tests of battery-powered emergency lighting were performed, as confirmed by both document review and interviews with the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Emergency Lighting Test
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors determined that the facility did not conduct or document the required annual 90-minute test of battery backup emergency lighting. This was confirmed by facility leadership during the survey process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙