K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
E

Non-compliance with Stairtower Door Standards

West Reading Skilled Nursing And Rehabilitation CeWest Reading, Pennsylvania Survey Completed on 12-11-2024

Summary

The facility failed to maintain the stairtower doors in compliance with NFPA 101 standards on one of four floors. During an observation, it was noted that the 4th floor 2D stairtower door had gaps greater than the allowed 3/16 inch, which was confirmed by the Director of Maintenance. Additionally, the 4th floor 1D stairtower door had broken panic hardware, was patched, and could not be opened as it was held closed with a 2 x 4 on the stairtower side. This was also confirmed by the Director of Maintenance during the interview.

Plan Of Correction

The Maintenance Director will repair the 4th floor hallway 2D stair tower door so there is no gap greater than 3/16 inch. The Maintenance Director will secure a contractor to replace the 4th floor hallway 1D stair tower door. The facility is requesting a Time-Limited Waiver for 1D replacement to be completed no later than 5/10/2025. The Maintenance Director or Designee will audit all stair tower doors to ensure that there are no gaps greater than 3/16 inch. The Maintenance Director or Designee will audit all stair tower doors to ensure that the hardware is functioning properly. The Maintenance Director or Designee will do random monthly audits every 90 days of all stair tower doors to ensure that there are no gaps greater than 3/16 inch and that the hardware is functioning properly. The Maintenance Director or Designee will present findings at the QAPI meetings for review and/or recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0225 citations
Improper Storage of Chairs in Exit Stair Towers
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

Surveyors observed that stair towers used as exits were not properly maintained, as multiple stair landings were being used for storage. Chairs were found stored on landings in several stairwells on one floor, and the Maintenance Director confirmed that these items were being kept within the stair towers.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Stairway Exits Blocked by Caution Rope and Signage
D
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

Stair tower doors on two building levels were found blocked by a caution retractable rope and signage instructing that the stairs were only for emergency use, which could delay resident egress. The maintenance director confirmed this setup during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Stairtower Door Failed to Latch Due to Improper Hardware
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

A stairtower door near the South Nurses' Station was found not to latch properly because of incorrectly mounted magnet hardware. This deficiency was confirmed by the DON and Director of Maintenance during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistive Rating of Exit Stair Enclosures
F
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

Surveyors found that all rated doors inside a stairwell enclosure between Personal Care and Skilled Nursing failed to positively latch, and a hollow wooden door of unknown fire rating was sealed within a fire-rated wall. These issues were confirmed by facility staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inoperative Stairway Path Interrupter on 2nd Floor Egress
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

An observation revealed that the electronic stairway path interrupter on the 2nd floor egress by the elevators was not functioning, which could cause individuals to miss the correct exit during an emergency. This issue was confirmed with the Maintenance Director and could affect a significant number of residents during a fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Stairtower Door Gap Deficiency
E
K0225 K225: Have stairways and smokeproof enclosures used as exits that meet safety requirements.
Short Summary

The facility did not maintain stairtower doors within the allowed gap margins on two floors. Observations revealed that the doors on the 1st and 2nd floors of Stairtower A had gaps exceeding 1/8 inch, confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙