K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.

Failure to Perform Emergency Lighting Tests at Generator

Kadima Rehabilitation & Nursing At PottstownPottstown, Pennsylvania Survey Completed on 12-09-2024

Summary

The facility failed to perform the required functional tests of the battery-powered emergency lighting source at the generator, which serves the entire component. During an observation on October 8, 2024, it was noted that the facility did not conduct the battery back-up emergency lighting test at the generator for 30 seconds monthly and 90 minutes annually. Additionally, the emergency light was found not mounted and was instead laying on an electrical duct. This deficiency was confirmed through an interview with the Director of Maintenance on the same day. A follow-up observation on December 9, 2024, revealed that the issue had not been corrected. The emergency lighting test had still not been performed, and the light fixture remained unmounted. The Director of Maintenance confirmed during interviews on December 9, 2024, that the deficiency identified in the initial observation had not been addressed.

Plan Of Correction

1. The facility is unable to retroactively conduct a 30-second monthly test or 90-minute annual test of the battery backup emergency lighting in the generator room before the survey. 2. The facility had a new Maintenance Director that started on 12/09/24. Maintenance or Designee will conduct a 30-second monthly test and a 90-minute annual test of the battery backup emergency lighting. The 90-minute test will be completed by 01/27/2025. Battery will be replaced as necessary. 3. Education will be provided to Maintenance staff regarding testing of the battery backup emergency lighting. Documentation of testing will be maintained in the Life Safety Book per regulation. 4. Maintenance Director or Designee will complete audits of routine testing monthly until substantial compliance has been achieved and quarterly thereafter. 5. Results of the audits will be presented to the QAPI committee for review and analysis for continued monitoring.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0921 citations
Failure to Maintain and Inspect Patient-Care Electrical Equipment
E
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

Surveyors found that fixed patient-care electrical equipment was not properly maintained or inspected in accordance with NFPA 99. In one room, a bedside remote had mismatched insulation and exposed wiring, and in another room, a call button receptacle had exposed low-voltage conductors. The Maintenance Director acknowledged both issues and reported that new bed remotes had been received but not yet installed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Annual Testing Documentation for Patient-Care Electrical Equipment
F
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

Surveyors found that the facility did not maintain required documentation showing that annual NFPA 99-compliant testing (including physical integrity, resistance, leakage current, and touch current tests) was performed on electrical equipment used for patient care. During record review with the Maintenance Director, no records could be produced to verify that this testing had been completed as required, and the Maintenance Director acknowledged the lack of documentation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Patient-Care Electrical Equipment per NFPA 99
D
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

Surveyors found that patient-care related electrical equipment was not inspected and maintained in accordance with NFPA 99 requirements. Biomedical inspection records showed that inspections were not current, and an observation in the gym revealed two microwaves, a toaster oven, and an "E Stem" device with overdue inspection stickers from 2024. During an interview, an assistant reported that this equipment was supplied by the corporate office and maintained by a different company, yet the items remained in use in a patient-care area without up-to-date inspections, affecting one of seven smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test Electrical Equipment Before Use
E
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

A portable blood pressure machine in the facility was found to be in use without undergoing the required Bio-Medical testing. The machine had been used daily for over two months, as confirmed by a staff nurse and the Director of Maintenance. This deficiency was acknowledged by the facility's administration during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Annual Electrical Inspections
F
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

The facility did not conduct the required annual inspection of electrical receptacles in resident care areas, affecting all resident bed locations. This deficiency was confirmed during an exit interview with the Administrator, Director of Maintenance, and Assistant.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Electric Beds as per Manufacturer's Guidelines
D
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

The facility did not ensure proper maintenance of electric beds as per the manufacturer's guidelines. During a survey, it was found that electrically operated beds were not inspected at the required intervals, and there was no documentation of formal inspections or maintenance. The Environmental Services Director acknowledged the lack of unique identifiers for beds and stated that beds were checked annually using a room audit form, but specific beds were not identified. This failure to adhere to maintenance requirements constituted a deficiency in compliance with NFPA 99 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙