K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
E

Failure to Conduct Annual Electrical Receptacle Inspection

Kadima Rehabilitation & Nursing At PottstownPottstown, Pennsylvania Survey Completed on 12-09-2024

Summary

The facility failed to conduct the required annual electrical receptacle inspection in resident care areas within one of two smoke zones. During a document review on October 8, 2024, it was found that there was no documentation verifying that electrical receptacles had been tested within the last 12 months. This was confirmed in an interview with the Director of Maintenance, who acknowledged that the receptacles in patient care areas had not been tested in the past year. Further observation on December 9, 2024, revealed that the issue had not been corrected, as confirmed again by the Director of Maintenance. The lack of testing and documentation indicates a failure to comply with the NFPA 101 Electrical Systems - Maintenance and Testing requirements, specifically regarding the testing of hospital-grade receptacles in patient care areas.

Plan Of Correction

1. Facility is unable to retroactively conduct annual electrical receptacle inspection in resident care areas. 2. A facility-wide audit of electrical receptacles will be completed. Maintenance Staff will be educated on the requirement to perform annual receptacle inspections. 3. Maintenance Director will complete annual electrical receptacle inspections by 01/27/2025. 4. NHA or designee will audit Life Safety Book semi-annually to confirm completion of annual inspections and that the documentation has been completed. The results of monitoring will be submitted to the QAPI committee for review and analysis of need for ongoing monitoring.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0914 citations
Failure to Perform and Document Required Annual Receptacle Testing
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors found that the facility did not perform or could not document required annual testing of electrical receptacles for tension and polarity in patient care areas, as mandated by NFPA 99. During record review with the Maintenance Director, no evidence was produced to show that hospital‑grade and other required receptacles had been tested at the specified intervals, and the Maintenance Director acknowledged this lack of documentation. This noncompliance with NFPA 99 Section 6.3.4 was cited as a deficiency affecting all occupants who rely on the facility’s electrical systems.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Required Polarity Testing of Electrical Receptacles
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors identified that the facility did not fully comply with NFPA 99 requirements for electrical receptacle maintenance and testing. Review of the electrical receptacle testing log showed that only tension testing was documented, with no evidence of polarity testing being conducted. During interview, the Maintenance Director confirmed that staff had never tested receptacle polarity. This deficiency was cited as affecting the entire facility and was noted as potentially causing faulty electrical equipment which can result in fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Electrical Receptacle Inspections
C
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not provide documentation verifying that annual inspections and testing of electrical receptacles in resident care areas were completed, as required by NFPA 99. This deficiency was confirmed by both the Administrator and the Director of Maintenance, and affected all smoke zones within the component.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test Electrical Receptacles at Resident Bed Locations
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not perform required testing of electrical receptacles at resident bed locations, including both hospital-grade and non-hospital grade outlets, as mandated by regulations. Documentation and interviews confirmed that testing for physical integrity, polarity, and grounding blade retention force was not conducted throughout the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test and Repair Hospital-Grade Electrical Receptacles
E
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Multiple hospital-grade electrical outlets in resident rooms failed inspection, and there was no documentation showing that these outlets were repaired or replaced as required. This deficiency was confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical System Testing and Installation
D
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility failed to accurately test electrical receptacles in resident care areas and lacked documented performance data. Additionally, improper installation of a power cord passing through the ceiling into interstitial space was observed, with a power strip used as permanent wiring above the fire sprinkler system, posing a potential fire hazard. These issues were confirmed by the Director of Maintenance and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙