K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
C

Failure to Inspect Rated Doors Annually

Kadima Rehabilitation & Nursing At PottstownPottstown, Pennsylvania Survey Completed on 12-09-2024

Summary

The facility failed to conduct the required annual inspection of all rated/labeled doors as mandated by NFPA 80, Standard for Fire Doors and Other Opening Protectives. During a document review and observation on October 8, 2024, it was revealed that the rated doors in all areas had not been inspected in the last 12 months. This deficiency was confirmed through an interview with the Director of Maintenance on the same day. Further observation on December 9, 2024, confirmed that the issue had not been corrected, as the rated doors still had not been inspected. The Director of Maintenance confirmed during interviews at 10:30 AM and 11:30 AM on December 9, 2024, that the deficiency remained unaddressed.

Plan Of Correction

1. The facility is unable to retroactively document inspection of rated/labeled doors. 2. Maintenance staff will be educated on the annual fire door inspection procedures. Rated doors will be inspected annually per regulations. 3. NHA and Maintenance Director will conduct annual audits to ensure inspections and corresponding documentation is completed per annual regulatory requirement. Audit results will be documented in the Life Safety Book. 4. Audit results and corresponding documentation will be presented to QAPI committee for review and analysis of need for ongoing monitoring.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0761 citations
Failure to Maintain Self-Closing Fire Door Mechanism
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

A corridor door with a self-closing mechanism leading to the clean utility room by the nurse's station failed to close or self-latch when tested, as confirmed by the Facility Manager. This failure to maintain the fire door in accordance with NFPA 101 and NFPA 80 standards resulted in a deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

Surveyors found that the facility did not provide documentation confirming that fire doors had been inspected within the required 12-month period. The Director of Maintenance confirmed that records of these inspections were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Annual Fire Door Inspections
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not perform a full annual inspection and testing of all rated swinging fire doors, as only the cross corridor fire doors were included while other rated doors, such as those for storage and utility rooms, were omitted. This was confirmed by the maintenance director during record review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Inspect Fire-Rated Attic Access Doors
F
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to inspect and maintain its fire-rated attic access doors according to NFPA 101 standards. During a fire safety tour, it was found that these doors were not included in the annual inspection, and the Plant Operations Technician was unsure of their inspection status. The Director of Plant Operations confirmed the oversight, acknowledging the findings during an exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Fire Door Inspections
C
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility failed to provide documentation of the annual fire-rated door inspection for six smoke compartments. This deficiency was identified during a document review, and the absence of documentation was confirmed during an interview with the Assistant Director of Nursing and the Maintenance Director. The lack of documentation indicates non-compliance with NFPA 80 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Test Fire Doors Annually
D
K0761 K761: To conduct inspection, testing and maintenance of fire doors by qualified individuals.
Short Summary

The facility did not maintain and test their fire doors as required by NFPA 101, with the last inspection recorded in December 2023. During a review, the Director of Continuum and Maintenance Supervisor acknowledged the absence of documentation for the annual inspection, indicating non-compliance with fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Pennsylvania

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Pennsylvania — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙