K0324 K324: Provide properly protected cooking facilities.
F

Failure to Perform Monthly Inspections of Fire Suppression System

Excel Care At WayneWayne, New Jersey Survey Completed on 12-13-2024

Summary

The facility failed to perform monthly inspections of the range-hood fire suppression system's wet chemical cylinder as required by NFPA 17 A: 2009 Edition and NFPA 96: 2011 Edition. During an observation, it was noted that the semi-annual inspection was conducted on December 2, 2024, and the inspection tag was new. However, the facility lacked documentation for the monthly inspections for the previous six months, specifically for June through November 2024. This oversight was confirmed during an interview with a staff member at the time of the observation. The deficiency was identified during a survey conducted on December 12, 2024, and was discussed with facility representatives at the Life Safety Code exit conference on December 13, 2024. The absence of monthly inspection documentation for the range-hood fire suppression system had the potential to affect all residents, as it is a critical component of the facility's fire safety measures. No further documentation was provided to demonstrate compliance with the required monthly inspections.

Plan Of Correction

1. Corrective Actions Accomplished for residents found to have been affected by the deficient practice: The Maintenance director reached the vendor which confirmed that the inspection was completed, however they do not keep previous tags. 2. Identification of residents who have the potential to be affected by the same deficient practice: All residents had the potential to be affected by the deficient practice. 3. Systemic changes to ensure that deficient practice does not recur: The U.S. FOIA (b) (6) was in serviced to conduct monthly audits of kitchen hood suppression inspections and automatic sprinkler separations. Maintenance/designee will complete audit inspections and sign off tags of suppression systems the first week of every month. Monthly audit logs will be submitted to the Administrator for review and kept in the Maintenance office. 4. Monitoring corrective actions: Corrective actions will be evaluated for effectiveness, and the plan of corrections will be integrated into the Quality Assurance Performance Improvement (QAPI) program. The Quality Assurance Performance Improvement Committee will review the monthly audit on a Quarterly basis x 12 months to ensure compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Kitchen Hood Inspections and Gas Appliance Restraints
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility failed to maintain the kitchen fire suppression system in accordance with NFPA standards, with only one documented kitchen hood inspection in the prior year and no additional inspection records available despite multiple requests. During the kitchen tour, surveyors also observed that gas-fired appliances lacked restraints to prevent overextension of gas lines when moved for cleaning or service, a finding confirmed by the Maintenance Director. This deficiency had the potential to affect 22 of the 69 residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New Jersey

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New Jersey — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙