Deficiencies in Smoke Barrier Wall Maintenance

Canterbury WoodsWilliamsville, New York Survey Completed on 01-08-2025

Summary

During a Life Safety Code survey, it was observed that the smoke barrier walls in the Occupational Therapy/Physical Therapy room and the main corridor were not maintained as required. Specifically, the smoke barrier walls were incomplete from floor to ceiling deck, lacked a 30-minute fire resistance rating, and were unable to resist the passage of smoke due to penetrations. In the Occupational Therapy/Physical Therapy room, a six-inch by six-inch open penetration and a three-foot by three-foot area of removed gypsum board were found. Additionally, a 22-foot by three-foot section of the smoke barrier wall was missing, exposing an unprotected steel beam. Further observations in the main corridor revealed a two-inch by two-inch penetration around electrical wires filled with orange foam, which the Facilities Director stated was not used by the facility. Another two-inch by two-inch open penetration was found around a gray electrical wire. The Facilities Director was unaware of these issues and stated that the Occupational Therapy/Physical Therapy room was undergoing remodeling. The architectural drawings confirmed that these walls were part of the facility's smoke barrier system, labeled as Smoke Area D, and were intended to provide fire and smoke protection.

Plan Of Correction

Plan of Correction: Approved February 6, 2025 Smoke Barrier walls in identified locations were not completely sealed from ceiling to roof deck. The Facilities Director had both the Facility Manager and Facility Supervisor seal all penetrations identified and sealed the open penetrations with fire sealant that is capable of maintaining the smoke resistance of the smoke barrier and meets the current NFPA standards. The Facilities Director inspected each area to ensure code compliance. All residents have the potential to be affected. The Facilities Director has reviewed requirements regarding smoke barriers. A review of the requirements of smoke barriers was also conducted by the Facilities Director with the Facility Manager and Facility Supervisor. The Facilities Supervisor will inspect all smoke barriers as part of the monthly environmental inspections. The Facilities Director will conduct monthly reviews of the inspection reports completed by the Facility Supervisor. The monthly inspections will be submitted by the Facilities Director at the bi-monthly Quality Assessment & Performance Improvement (i.e., QAPI) Committee meetings. The Facilities Director will be responsible for the ongoing compliance of this plan.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other State4FAD34050DA90602 citations

No citations found matching the criteria.

Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙