F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
E

Environmental Deficiencies in Facility's Common Areas

Waterview Nursing Care CenterFlushing, New York Survey Completed on 12-09-2024

Summary

The facility failed to maintain a safe and functional environment for residents, staff, and the public, as observed during a recertification survey. Several deficiencies were noted in various areas of the facility, including the Lobby area, hallways, and nursing stations. Specifically, the bathroom near the Main Dining Room had holes in the wall, a rusty call bell panel, and broken molding. Additionally, cable wires at one nurse station were covered in dirt and dust, while the second-floor nurse station had torn vinyl armrests on chairs and a desk with broken Formica paneling. Further observations revealed that the third-floor nurse station had peeling wallpaper, a desk with rough edges, and a malfunctioning bottom drawer. The staff bathroom in this area also had a leaking faucet. The 1 North Nursing station was noted to have dusty areas and unpainted ceiling patches. The facility's policy emphasizes providing a clean, comfortable, and homelike environment, but the administrator acknowledged the environmental concerns and stated that corrective actions were not yet documented or implemented.

Plan Of Correction

Plan of Correction: Approved January 2, 2025 Immediate Correction 1) As of 12/31/24, the facility repaired the holes in the wall of the bathroom near the Main Dining Room, repainted as needed and replaced the rusty call bell panel and broken molding. 2) As of 12/31/24, the West unit nurse station was thoroughly cleaned specifically all cable wires to remove accumulated dirt and dust. 3) As of 12/31/24, On the 2nd Floor nursing station, Maintenance/Housekeeping department replaced the two black swivel chairs with torn vinyl armrests and repaired the desk with broken and rough-edged Formica paneling. 4) As of 12/31/24, On the 3rd floor nursing station, Maintenance/Housekeeping department replaced the peeling and torn wallpaper underneath the desk area, repaired the desk with rough bottom edges and broken Formica panels, repaired the bottom desk drawer to ensure proper closure and fixed the leaking and loose faucet in the staff bathroom. 5) As of 12/31/24, On the North unit nursing station, the Maintenance/Housekeeping department cleaned the dusty areas thoroughly and patch/painted the unpainted ceiling areas. 6) The above Immediate repairs and replacements were documented in the maintenance log and overseen by the Maintenance Director to ensure timely completion. Identification of Others 1) The Director of Maintenance and Housekeeping will conduct a facility-wide environmental audit to identify other areas that may not meet the standards of a safe, functional, sanitary, and comfortable environment. 2) Include all common areas, resident rooms, nursing stations, and staff areas in the audit. 3) Document all findings and create a prioritized corrective action plan for each identified issue. Systemic Changes 1) Review and revision of the facility's Environmental Policy to include: - Detailed cleaning schedules for all areas, including nursing stations and common spaces. - Timelines for routine inspections of furniture, fixtures, and equipment to ensure functionality and safety. - Clear procedures for promptly addressing and documenting maintenance requests. 2) Provide in-service training to Housekeepers, Maintenance Workers, RN's, LPN's and CNA's on the importance of maintaining a safe, clean, and homelike environment. 3) Emphasize protocols for reporting environmental concerns promptly to the Maintenance Director through in servicing and education. 4) Establish an annual budget and timeline for replacing worn or damaged furniture and equipment. 5) Maintain a vendor proposal log and receipts to ensure accountability for all purchases and replacements. Quality Assurance 1) The Maintenance Director or designee will develop and conduct a weekly environmental rounds audit tool focusing on areas cited in the deficiency and other high-traffic locations. 2) Conduct monthly audit of common areas, resident rooms, and nursing stations to ensure ongoing compliance. 3) Solicit feedback from residents, families, and staff through surveys and suggestion boxes to identify additional environmental concerns or improvements. 4) Audits will be completed by the Maintenance and Housekeeping weekly x 4 weeks; monthly x 3 months; and quarterly for x 1 year. Any negative findings will be addressed immediately. 5) Findings will be brought to the QAPI quarterly meeting for tracking of facility compliance. Person Responsible for this Ftag: 1) The Administrator.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0921 citations
Loud Violent TV Programming in Secured Unit Dining Area
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

A large-screen TV in the secured unit dining room was playing a loud, violent movie during meals, with screaming, gunfire, crying, and dark scenes visible to residents seated nearby. Two residents with dementia-related cognitive impairment and behavioral issues were directly affected; one became angry and complained the TV was too loud and too dark, while another repeatedly turned off the lights and struck out at an NA when blocked. An LPN, RN, AD, and DON stated the programming was not appropriate for residents with dementia and could increase anxiety or agitation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Dirty G-tube Pump and Room Floor
D
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Dirty G-tube Pump and Room Floor: A resident with Parkinson’s disease, DM, and impaired cognition was observed sleeping in bed while connected to a turned-off G-tube pump that had visible dried milk residue, and the room floor also had visible dried milk residue. A CNA confirmed the pump and floor were dirty, and an LVN stated food or milk drippings should be cleaned right away. RN review showed the care plan called for a safe environment with a floor free from spills and clutter, and the facility did not follow its cleaning and disinfection policy.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Poorly Maintained Environment
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and Poorly Maintained Environment: A hole in the ceiling on Hall 100, a detached baseboard in a shower room on Hall 300, dim lighting in the secure unit dining room, and a leaking kitchen ceiling were observed in the LTC facility. Staff and management interviews showed the issues were known or reported inconsistently, and maintenance logs did not document several of the problems. The kitchen leak was being collected in a pot near the food prep area, and the DM stated the kitchen leaked when it rained.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Nonfunctional Bathroom Fixtures
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and nonfunctional bathroom fixtures were observed on two nursing units and in one resident room. A resident reported a broken faucet, and staff observed a replacement knob that wiggled and did not work properly. In one shower room, the hot and cold indicators were reversed, and in another shower room, the drain cover was missing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe and Unclean Unit Environment
D
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe and Unclean Unit Environment: The 200 unit had marred walls, chipped door trim, a large hole in a resident room wall, missing drywall near the offices, and dirt buildup on baseboards, floors, and around the elevator. The dining room and elevator area also had debris buildup, and the elevator door frame wrap was hanging off on both sides. An HSKP staff member stated the facility was down a housekeeper and floors should be cleaned daily.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsafe Resident Room Conditions Due to Nonfunctional A/C and Biological Growth
E
F0921 F921: Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
Short Summary

Unsafe resident room conditions were identified when multiple rooms had nonfunctional A/C units, temperatures above 81 degrees, and unsealed openings around replacement units. A resident with paraplegia, polyneuropathy, chronic pain, and TBI reported living in a room without working A/C for weeks, while staff said several rooms had been hot for months and administration knew about the issue. Surveyors also observed biological growth inside one A/C unit and on a ceiling tile above a sink in a room occupied by a resident with respiratory concerns.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across New York

Get a heads-up on the newest immediate-jeopardy (J–L) citations in New York — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release August 26, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report