F0908 F908: Keep all essential equipment working safely.
F

Inconsistent Hot Water Temperatures in Facility

Dove Healthcare - SpoonerSpooner, Wisconsin Survey Completed on 08-21-2024

Summary

The facility failed to maintain its steam heated hot water system in a safe operating condition, resulting in fluctuating water temperatures that were often inadequate for resident use. The facility's Water Management Program Policy and Procedure requires that hot water temperatures be maintained between 140 to 150 degrees Fahrenheit in holding tanks, with safe bathing temperatures at 100 degrees Fahrenheit. However, observations and interviews revealed that the water temperatures in resident rooms and showers were frequently below the required levels, with temperatures ranging from 80 to 100 degrees Fahrenheit during the surveyor's checks. Interviews with residents and staff confirmed the inconsistency in water temperatures. Residents reported that the water was sometimes not hot enough for bathing, and staff noted that it often took a long time for the water to reach a warm temperature. The Director of Maintenance acknowledged that the facility's hot water system, installed in the 1960s, had ongoing issues, including a sticking steam valve and a mixing valve that required frequent adjustments. Despite these known issues, there had been no attempts to repair the system. The Director of Maintenance indicated that the system was checked regularly, and adjustments were made as needed. However, the water temperatures did not remain consistent throughout the day, as evidenced by the surveyor's findings. The Nursing Home Administrator was informed of the issues, and it was noted that the water temperature problems would be reported to the corporate office for further action.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Resources

Below are regulatory guidelines relevant to this citation:

See other F0908 citations
Inoperable Commercial Washer in Laundry Department
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

In the laundry department, 1 of 2 commercial washers was out of service for more than 8 months, leaving only 1 washer available for resident laundry. Laundry Aides stated they used the working washer for all residents and that keeping up with timely laundry services was sometimes challenging with only 1 machine.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hoyer Lift Batteries Not Maintained in Safe Operating Condition
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

A resident who required a mechanical lift for transfers experienced repeated Hoyer lift battery failures during transfers, including one observed transfer where the lift stopped working while he was being lowered. Staff reported that lift batteries were often not charged, that overnight staff were responsible for charging them, and that they sometimes used the emergency release to lower the resident when the battery died. The DON and other staff confirmed the batteries were not consistently checked or maintained, and the maintenance supervisor said batteries were only replaced occasionally.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Flooring Renovation Started Before Construction Review Approval
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Flooring Renovation Started Before Construction Review Approval: The facility removed carpet and installed laminate flooring in resident areas before receiving DOH Construction Review Services approval. The Administrator said the second-floor west unit remodeling had already been completed and residents were moved to another unit during the work. Notices to residents described planned flooring replacement, observation confirmed new wood flooring in the hallway and resident rooms, and a resident said they were relocated for at least two weeks. The Regional Plant Operations Director stated the approval was still pending and that they were unsure of the approval process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Laundry Equipment Not Maintained in Safe Operating Condition
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Laundry equipment was not maintained in safe operating condition. A resident with ESRD on dialysis reported that clothes came back stinking, while the Laundry Supervisor said the industrial washer kept breaking down, hot water was not getting hot, the wrong soap was being used for resident clothing, and the department lacked a hopper for washing soiled linens. Observation showed a small washer overfilled with sheets, and staff gave mixed reports about washer breakdowns and linen shortages.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Mechanical Lift Found With Exposed Charging Cord
D
F0908 F908: Keep all essential equipment working safely.
Short Summary

Mechanical lift equipment on the 3rd floor was observed with exposed black and red inner cords from the grey charging cord hanging out. An RN said the lift should not be used if the cords are exposed, and the DON stated such equipment should be reported to maintenance and removed from the floor for safety precautions. The Maintenance Director confirmed the outer grey cord protects the inner cords, and the maintenance log showed no repair report for the lift.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Expired Ambu Bags Found on Two Crash Carts
E
F0908 F908: Keep all essential equipment working safely.
Short Summary

Expired Ambu Bags Found on Two Crash Carts: The facility failed to ensure two crash carts were in safe operating condition when an Ambu bag on the First Floor Crash Cart and an Ambu bag on the Second Floor Crash Cart were both found expired. RN staff confirmed the expired equipment and acknowledged the carts were not maintained as required by the facility's crash cart management process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Citation search

Search every citation & Plan of Correction

Go to search
Citation watch

Track new serious citations across Wisconsin

Get a heads-up on the newest immediate-jeopardy (J–L) citations in Wisconsin — where surveyors are focused right now.

Free · about one email a month

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release July 29, 2026) and official state health department websites — never guesswork.

In your survey window? See what surveyors are citing.

The Survey-Prep Report maps your facility's risk from 12 months of CMS and state citation data — what's being cited around you and what to check first. $129 one-time.

Get the Survey-Prep Report
An unhandled error has occurred. Reload 🗙